Explanation (Text editor for one specific "display unit"):
Zone-Address column
Shows the already programmed alarm points (e.g. 001-01, 001-02, 002-01 etc.).
Shows the already programmed zones, i.e. I/O unit 3361 zone line inputs and 8 zones
expansion board 4580 zone line inputs programmed with address "00" (i.e. as ZZZ – 00).
Text in Control Unit column (cannot be edited here)
Shows the already programmed texts for each alarm point / zone. This is only information
and cannot be edited. These texts will be displayed in the CIE and all "display units" 1736
and 1728 if there are no other texts programmed in the "Text column".
Text column
The text to be shown in this specific "display unit" for the alarm point / zone, has to be
typed (edited) here. In this "display unit" the text in the "Text" column will now be shown
instead of the text in the "Text in Control Unit" column, for the alarm point / zone
respectively.
17.25.2

Downloading alarm texts to the Display Units 1728 / 1736

The "display units" have to be connected to FT1020G3 and the address and mode
to be set in the "display units".
The texts will then be downloaded at the same time as the FT1020G3 site specific data
(SSD) is downloaded via EBLWin
The texts can as an alternative be downloaded in one "display unit" at a time but the PC
(with EBLWin) has nevertheless to be connected to FT1020G3.
141
S/W mode xxxx – 1587. (xxxx = e.g. 1728)
142
In the "Download SSD to Control Unit" dialog box the "Download to FBP / AAU / EPU" check box has to be selected. (As an
alternative the "Modified FBP / AAU / EPU only" check box can be selected.)
Technical/Programming Manual
142
.
125
FT1020G3 Rev 2.2.1