CHAPTER 4: INTERFACES

Annunciator

Annunciator operation
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 43: Equipment manager battery monitor alarms example
The annunciator is a color TFT panel located that emulates the functionality found in a
conventional annunciator unit.
The annunciator provides indications on the status of system alarm points. It also displays
self-test messages and product information for the unit.
Figure 44: Typical annunciator display
There are three control buttons at the bottom of the display.
The Next Page button cycles through the pages of alarms and to the self-test page.
The Next Alarm button cycles horizontally through the current alarms, from left to
right, starting with the first row of alarms. A graphical frame borders the current
status box to indicate the selected alarm. The front panel display is dynamically
controlled according to the selected alarm.
The Ack button controls the state of the alarms.
The annunciator alarm sequence conforms to ISA 18.1-1979 (R1992) standard, type R.