IEC 61850 COMMUNICATIONS

Report control configuration

124
IEC 61850 GGIO4 Analog 1 Maximum
Range: –1000000000.000 to 1000000000.000 in steps of 0.001
Default: 0.000
These settings specify the maximum value for each analog value. Refer to IEC 61850-7-1
and IEC 61850-7-3 for additional details. This maximum value is used to determine the
deadband. The deadband is used in the determination of the deadbanded magnitude
from the instantaneous magnitude.
These settings are stored as IEEE 754 / IEC 60559 floating point numbers. Because of the
large range of these settings, not all values can be stored. Some values may be rounded
to the closest possible floating point number.
IEC 61850 buffered and unbuffered reporting is provided in the GGIO1 logical nodes (for
binary status values) and MMXU1 to MMXU4 (for analog measured values). Report settings
can be configured using the EnerVista UR
software, or via an IEC 61850 client.
Select the Settings > Communications > IEC 61850 > Report Control Configuration
menu item to open the IEC 61850 report configuration window.
Figure 94: IEC 61850 report control configuration
The following settings are available for each report. Up to 12 reports can be configured.
Changes to the report configuration will not take effect until the D90
RptID
Range: up to 66 alphanumeric characters
Default: empty
This setting specifies the name fo the IEC 61850 report.
OptFlds
Range: 0 to 65535 in steps of 1
Default: 0
This setting specifies a bitmask that selects the option fields. The following bits are
Plus
supported by the D90
Bit 1: sequence-number.
Bit 2: report-time-stamp.
Bit 3: reason-for-inclusion.
Bit 4: data-set-name.
Bit 5: data-reference.
Bit 6: buffer-overflow (for buffered reports only).
Bit 7: entryID (for buffered reports only).
Bit 8: conf-revision.
Plus
Setup software, substation configurator
.
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: COMMUNICATIONS
Plus
is restarted.