Obh629 - Mitsubishi Electric MUZ-SF25VE-E1 Service Manual

Outdoor unit
Hide thumbs Also See for MUZ-SF25VE-E1:
Table of Contents

Advertisement

J Check of power supply
Disconnect the connector between
compressor and intelligent power
module.
Turn ON power supply and press
EMERGENCY OPERATION switch.
Does The left lamp of OPERATION
INDICATOR lamp on the indoor unit
light up?
Yes
Is there voltage 260 - 370 VDC
between DB61 (+) and DB61 (–)
on the inverter P.C. board?
(Refer to 11-6.1.)
No
Check the electric parts in main circuit.

OBH629

Rectify indoor/outdoor
connecting wire.
Yes
Is there voltage 230 VAC
between the indoor terminal
No
block S1 and S2?
Dose LED on the inverter P.C.
board light up or fl ash? (Refer
Yes
to 11-6.1.)
Yes
If light up, OK.
If fl ash, refer to 11-3.
38
Replace the indoor
electronic control P.C.
No
board.
Replace the inverter
No
P.C. board.
260 - 370 VDC
DB61
Inverter P.C. board
(Solder side)