Middle Atlantic Products UPS-2200R-HH User Manual

Middle Atlantic Products UPS-2200R-HH User Manual

Rackmount ups rackmount uninterruptible power supply

Advertisement

UPS-2200R-HH/UPS-2200R-HHIP
RACKMOUNT UNINTERRUPTIBLE POWER SUPPLY
THANK YOU
Thank you for purchasing the UPS-2200R-HH/UPS-2200R-HHIP Rackmount UPS. The UPS
provides battery backup during power outages, automatic voltage regulation during periods
of inconsistent utility power and surge protection.
IMPORTANT
Please read this manual before removing the UPS from the shipping carton and before making any
connections to and operating your UPS.

USER MANUAL

082410-01
U L
C
US
R
LISTED
I-00462
Rev D

Advertisement

Table of Contents
loading

Summary of Contents for Middle Atlantic Products UPS-2200R-HH

  • Page 1: User Manual

    RACKMOUNT UNINTERRUPTIBLE POWER SUPPLY LISTED 082410-01 THANK YOU Thank you for purchasing the UPS-2200R-HH/UPS-2200R-HHIP Rackmount UPS. The UPS provides battery backup during power outages, automatic voltage regulation during periods of inconsistent utility power and surge protection. IMPORTANT Please read this manual before removing the UPS from the shipping carton and before making any connections to and operating your UPS.
  • Page 2: Table Of Contents

    Important Safety Instructions ........Middle Atlantic Products Green Power UPS Technology ....
  • Page 3: Important Safety Instructions

    IMPORTANT SAFETY INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS The lightning flash with the arrowhead symbol, within an equilateral triangle, is intended to alert the user to the presence of uninsulated dangerous voltage within the product’s enclosure that may be of sufficient magnitude to constitute a risk of electric shock.
  • Page 4: Middle Atlantic Products Green Power Ups Technology

    UPS will operate under Battery or AVR Mode. Under this condition, Green Power UPS and a traditional UPS would operate about the same. On average, utility power operates 88% of the time and the Middle Atlantic Products Green Power Technology will work in its money/energy saving Bypass Mode.
  • Page 5: Unpacking

    UNPACKING CAUTION: DO NOT LIFT THE UPS WHILE HOLDING THE FRONT FACE OF THE UNIT. THIS MAY DAMAGE THE UNIT. ALWAYS LIFT THE UPS BY HOLDING IT BY BOTH SIDES. LIFT OUT OF BOX WHILE HOLDING BOTH SIDES OF LIFT OUT OF BOX WHILE HOLDING BOTH SIDES OF The UPS is very heavy and should be handled by two (2) people.
  • Page 6 INSTALLATION AND MOUNTING CONTINUED CAUTION: THIS UNIT IS HEAVY, LIFT CAREFULLY One Person Installation: 1) Determine mounting location. 2) Install the Rear Mounting Brackets as shown. One Bracket is longer then the other to provide guidance when doing a one person installation. These brackets are interchangeable. (FIGURE A) IMPORTANT NOTE: Rear Mounting Brackets mount between the two corresponding rackspaces in the front of the enclosure.
  • Page 7: Front Panel Description

    FRONT PANEL DESCRIPTION LCD display: The LCD display indicates a variety of UPS operational conditions (see page 15 for LCD display definitions). Power Switch: On/off switch to turn UPS on and off. LCD display toggle button: Toggles between a variety of UPS operational conditions (see page 15). REAR PANEL DESCRIPTION Reset Non-Critical Load...
  • Page 8 REAR PANEL DESCRIPTION CONTINUED Reset Non-Critical Load Wiring Fault Reset Reset Input: Expansion Port 125V Non-Critical Load Critical Load 125VAC 60Hz 125VAC 1650W 60Hz - 16A 60Hz - 16A 2150VA E325394 6G48 Serial Port Primary Secondary Site Wiring Fault Input LED Indicator: This LED will illuminate to warn the user that a wiring problem exists within the AC mains electrical supply receptacle, such as reversed wiring.
  • Page 9 REAR PANEL DESCRIPTION CONTINUED Critical Load Receptacle: Critical load receptacle, NEMA 5-20R. Critical Load Output Connector Knock-Out: 125 VAC, 50/60 Hz, 16A. (Trade size ½”) Non-Critical Load Output Connector Knock-Out: 125 VAC, 50/60 Hz, 16A. (Trade size ½”) Reset Wiring Fault Circuit 1 Non-Critical Load Reset Reset...
  • Page 10: Output Wiring Instructions

    INSTALLING HARDWIRED OUTPUTS WIRING TO OUTPUT CIRCUITS USING INSTALLER SUPPLIED #12AWG MINIMUM #10AWG MAXIMUM CONDUCTORS. WIRING INSTALLATION MUST BE PERFORMED BY QUALIFIED PERSONNEL UPS POWER MUST BE TURNED OFF, AND MAINS POWER MUST BE DISCONNECTED PRIOR TO WIRING 1) Remove the J-Box cover (6) and the knock-out cover from the desired output (21 &...
  • Page 11: Installing Hardwired Input

    INSTALLING HARDWIRED INPUT (MODELS UPS-2200R-HH/UPS-2200R-HHIP ONLY) 1) Remove the protective shipping bushing from the hardwired input knock-out. 2) Grab and hold the three conductors at the end of the hardwired input cord (23). Gently slide the flexible conduit until the snap-in connector (24) meets the knock-out on the UPS.
  • Page 12: Setup Of (Nic) Ups-Ipcard

    2) After the installation is complete, run the “Middle Atlantic UPS-IPCARD Setup Utility” program. Under “All Programs”, select “Middle Atlantic Products > UPS-IPCARD”. 3) The main screen of the SNMP Card Configuration Tool program is shown in (FIGURE A). The configuration tool will display all Middle Atlantic UPS Network Interface Cards present on the network.
  • Page 13 SETUP OF UPS-IPCARD CONTINUED 4) Select the SNMP card you are setting up. Click on the Tools menu and select “Device Setup” or double click the SNMP card you want to configure. 5) You can modify the IP Address, Subnet Mask, and Gateway address for the Device MAC Address listed in the Device Network Settings window, as shown in (FIGURE B).
  • Page 14 SETUP OF UPS-IPCARD CONTINUED Method 2: Using a Command Prompt 1) Obtain the MAC address from the label on the UPS Network Interface Card rear panel. Each UPS Network Interface Card has a unique MAC address. 2) Use the ARP command to set the IP address. Example: To assign the IP Address 192.168.20.240 for the UPS Network Interface Card, which has a MAC address of 00-0C-15-00-00-01 you will type in the following command prompt from a PC connected to the same network as the UPS Network Interface Card.
  • Page 15: Lcd Display Definitions

    To clear the overload, first turn the power off on each equipment and unplug from the AC outlets one at a time, until the overload icon disappears and the alarm stops. Fault Icon: This icon appears if there is a problem with the UPS. Contact Middle Atlantic Products at 1-800-266-7225 for further help and support.
  • Page 16: Battery Charging

    BATTERY CHARGING The UPS is shipped from the factory with its internal battery fully charged. However, the battery may lose some charge during shipping and storage. Recharging the battery for at least four hours is recommended to ensure that the battery's maximum charge capacity is achieved. The UPS is equipped with an auto-charge feature.
  • Page 17: Operation

    OPERATION CAUTION: DO NOT plug a laser printer, copier, space heater, vacuum, paper shredder or other large electrical device into the UPS. The power demands of these devices will overload and possibly damage the UPS. 1) Plug the UPS into a grounded wall receptacle. Ensure the wall receptacle is protected by a fuse or circuit breaker and does not service other equipment with large electrical demands (i.e.
  • Page 18: General Status Mode

    GENERAL STATUS MODE 1) Press the Select button on the front panel to view each UPS status item listed in Table 1. Each item will display in the order shown. NOTE: The LCD display backlight will automatically turn off if the Select button is not pressed for more than 30 seconds.
  • Page 19 FUNCTIONS SETUP MODE (Continued) DEFAULT SETTING FUNCTION DESCRIPTION The time delay switching from battery mode to Delay Time line mode. There are 9 different settings: (0, 0.5, 1.0, 1.5, 2.0, 2.5, 3.0, 3.5, 4.0) seconds This function defines the number of external 0 (no external battery Number of Expansion battery packs connected to the UPS: (one - ten)
  • Page 20: Battery Replacement

    BATTERY REPLACEMENT Contact your dealer or call the number in this manual for information on battery replacement. Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of personnel who are knowledgeable about batteries and their precautions. Servicing of the battery can only be performed by trained personnel.
  • Page 21 BATTERY REPLACEMENT (Continued) CAUTION: The battery is heavy, use caution when removing 1) Remove the front panel by removing six screws then grasping it on the left hand side and pulling it away from the unit. Remove the right side of the panel to detach it from the unit. REMOVE FRONT PANEL 2) Remove the retaining screws securing the cable protection cover to the UPS and remove...
  • Page 22: Optional External Battery Connection

    BATTERY REPLACEMENT (Continued) 4) Remove three battery retaining screws (2 on left side, and 1 on the right side) and pull the battery out using the handle. REMOVE 2 SCREWS HANDLE REMOVE 1 SCREW 5) Insert replacement battery (Part No. UPS-RBP) and perform steps 2 - 4 in reverse. To reinstall the faceplate, reinstall six screws.
  • Page 23: Troubleshooting

    1. Recharge the battery by leaving the UPS 1. Battery is not fully charged. The UPS does not plugged in. perform the expected 2. Contact Middle Atlantic Products about 2. Battery is degraded. runtime. replacement batteries at 1-800-266-7225. 1. Turn the UPS off. Wait 10 seconds and 1.
  • Page 24: Troubleshooting

    TROUBLESHOOTING NETWORK INTERFACE CARD Problem Solution 1. Check the LED status, the normal condition is both yellow and green led is on. If green LED is off: Check if the UPS Network Interface Card is Unable to configure the UPS properly seated in the UPS and the UPS power is on.
  • Page 25: Technical Specifications

    TECHNICAL SPECIFICATIONS Capacity (VA) 2150 Capacity (Watts) 1650 Input Cord Length & Plug Type 3ft. Hardwired Input Voltage Range 80 VAC - 150 VAC Input Frequency Range 50/60 Hz +/- 3 Hz (auto sensing) Output On Battery Output Pure Sine Wave at 120 VAC +/- 7% Voltage On Battery Output 50/60 Hz +/- 1%...
  • Page 26 TECHNICAL SPECIFICATIONS CONTINUED Warning Diagnostics Power On, Wiring Fault, LCD Display (Using Battery, AVR, Load Level, Indicators Battery Level) Audible Alarms On Battery, Low Battery, Overload Environmental Operating Temperature 32º F to 104º F (0º C to 40º C) Operating Relative 0 to 95% Non-Condensing Humidity Communication...
  • Page 27: Estimated Runtime

    WARRANTY Middle Atlantic Products, Inc. (the "Company") warrants the UPS-2200R-HH Uninterruptible Power Supply product to be free from defects in material or workmanship under normal use and conditions for a period of (3) three years from date of shipment by the Company, with the following exception: the internal battery is covered for (2) two years.