EQUIPMENT SELECTION PROCEDURE
Cooling / Heating Correction Factors
For the Single Zone Mega Wall Mounted system, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit.
Also, determine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity
correction factors as shown in Figures 17 through 20. Multiply the correction factors by the cooling or heating capacity obtained from the
capacity tables using design conditions. The resultant is the NET cooling or heating capacity.
Figure 17: LS090-240HEV1 Cooling Coefficient Factor.
Cooling
100
90
24.6
Figure 18: LS090-240HEV1 Heating Coefficient Factor.
Heating
100
95
24.6
50 | APPLICATION GUIDELINES
9k,12k
49.2
Total Pipe Length (ft)
9k,12k
49.2
Total Pipe Length (ft)
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
18k,24k
65.6
18k,24k
65.6