Extended Parameter Setting
The RVS-DX incorporates a parameter, "WIDER SETTINGS", in the special Features Parameters.
If the RVS-DX is significantly larger than your motor, you can enable the "wider settings" to extend
parameter settings of the following:

Extended Parameter Settings

Parameter
Initial Voltage
Current Limit
Acceleration Time
Deceleration Time
Max. Start Time
RVS-DX, Digital Soft Starter Instruction Manual—04/01/04
4-6
Original Setting Range
10-50%
100-400%
1-30 seconds
0-30 seconds
1-30 seconds
Extended Setting Range
10-80%
100-500%
1-90 seconds
0-90 seconds
1-250 seconds