Optional Accessories - Viessmann VITODENS 200-W Technical Data Manual

Natural gas and liquid propane gas gas-fired wall-mounted condensing boiler
Table of Contents

Advertisement

Vitodens 200-W, B2HB 19 to 35 Technical Data

Optional Accessories

Supply Temperature Sensor
(strap-on sensor, included with mixing valve actuator
accessory kit),
- when storing
or transporting:
Installed with a strapping band.
Cable length 19.7 ft. (6 m), ready to plug in.
Max. ambient temp.
- at operation:
- when storing
or transporting:
Room Temperature Sensor,
Separate room temperature sensor as supplement to the
Vitotrol 200A and 300A; to be used if the Vitotrol 200A
or 300A cannot be installed inside the main living room
or in a suitable position where the unit can capture and
adjust the temperature.
Installation in the main living room on an internal wall
opposite radiators. Never install inside shelf units,
recesses, immediately by a door or heat source
(e.g. direct sunlight, fireplace, TV set, etc.).
Connect the room temperature sensor to the Vitotrol
200A or 300A.
Electrical connection:
- 2-wire cable with a wire size of min. AWG 18 copper
- The cable length between the control unit, remote
control unit and room temperature sensor must not
exceed 98 ft. (30 m)
Max. ambient temp.
- at operation:
- when storing
or transporting:
-4 to+158° F (-20 to+70ºC)
32 to 212ºF (0 to 100ºC)
-4 to+149ºF (-20 to+70ºC)
32 to 104ºF (0 to 40ºC)
-4 to+149ºF (-20 to +65ºC)
Mixing Valve Motor Kit
The mixing valve actuator is mounted directly on the
Viessmann ¾ to 2½" mixing valve.
The mixing valve actuator is a motor-driven control unit.
The rotational direction is reversible.
Rated voltage:
Rated frequency:
Power consumption:
- at operation:
application in living areas and installation sites
(normal ambient conditions)
-storage & shipping:
Accessories
120 VAC
60 Hz
4W max. ambient temperature
32ºF to 104ºF (0ºC to 40ºC)
-4ºF to 149ºF (-20ºC to 65ºC)
21