Detroit Radiant Products UH-30 Installation, Operation, Maintenance And Parts page 19

Uh series
Table of Contents

Advertisement

UH
Series
Chart 3.4 •
Maximum capacity for Schedule 40 Metallic pipe, in CFH
Pipe
1/2"
Length
Nat
L.P.
(feet)
10'
132
20'
92
30'
73
40'
63
50'
56
60'
50
70'
46
80'
43
90'
40
100'
38
125'
34
150'
31
175'
28
200'
26
The UH Series heater is equipped to receive a gas supply line nipple of ½"NPT Schedule 40 metallic
pipe. All piping must be installed in accordance with the requirements outlined in the National Fuel Gas
Code ANSI/Z223.1 (latest edition) or CSA-B149.1 and B149.2. Support all gas supply piping with pipe
hangers, metal strapping, or other suitable material. Do not rely on the heater to support the gas pipe.
When connecting piping to the unit, the use of a thread joint compound is required. The thread
compound (pipe dope) shall be resistant to the action of liquefied petroleum gas or any other chemical
constituents of the gas to be conducted through the piping. Use of Teflon
Install a ground joint union with a brass seat and a manual shut off valve adjacent the unit for
emergency shut off and easy servicing of controls. A 1/8" NPT plugged tap that is accessible for a test
gauge connections is also recommended, as illustrated in Figure 3.4.
A sediment trap must be installed in the supply line in the lowest spot prior to connecting to the heater.
The trap length shall be at least three inches long. Ideally, the trap would be installed as close as
possible to the shut off, as shown in Figure 3.4.
3/4"
Nat
L.P.
Nat
86
278
182
520
60
190
124
350
48
152
99
285
41
130
85
245
37
115
75
33
105
69
195
30
96
63
180
28
90
59
26
84
55
160
25
79
52
150
22
72
47
130
20
64
42
120
18
59
39
17
55
36
100
WARNING
!
Always use two (2) opposing wrenches to tighten mating pipe connections
to prevent excessive torque on the gas valve and manifold pipe. Excessive
torque can damage the valve and/or misalign the orifice, resulting in fire,
explosion, serious injury or death.
3.0
Installation
1"
1-1/4"
L.P.
Nat
340
1050
229
730
186
590
160
500
215
141
440
127
400
118
370
170
111
350
105
320
98
305
85
275
78
250
110
72
225
65
210
19
Gas Supply Installation Instructions
1-1/2"
L.P.
Nat
L.P.
686
1600
1046
477
1100
719
386
890
582
327
760
497
288
670
438
261
610
399
242
560
366
229
530
346
209
490
320
199
460
301
180
410
268
163
380
248
147
350
229
137
320
209
tape is not permitted.
®
2"
Nat
L.P.
3050
1993
2100
1373
1650
1078
1450
948
1270
830
1150
752
1050
686
990
647
930
608
870
569
780
510
710
464
650
425
610
399