Explosive -Proof PT for FLIR Uncooled IR Cameras EV3000- PT-EXIR Operation and Maintenance Manual United Vision Solutions, LLC.
Page 2
TABLE OF CONTENTS Part A PTZ 1. Introduction 2. Specifications 3. Installation 4. Operation 5. Dimensional diagram 6. Communications & Protocol Part B FLIR IR Cameras Part C Conduit Sealing Instructions for Equipment in Hazardous Locations Warranty $SSHQGL[ I IR cameras maintenance $SSHQGL[ II Glossary...
Page 3
EV3000-PT-EXIR ideal for either indoor or outdoor applications. The system has an absolute operating temperature range of –25° to +50°C. The EV3000-PT-EXIR is Pan Tilt Driver & IR Camera with built-in receiver using Pelco-D protocol, powered by External 24 VDC Power Cable, RS-485 Communication lines, and Video Cable.
Page 4
6SHFLILFDWLRQV G G ENERAL Construction Aluminum / Sainless steel Finish Electro polish Viewing Ge Window for cooled and uncooled Designed and manufactured to meet the UL/cUL Hazardous Locations Listed per NEC Division and Zone requirement Class I, Divisions I and II, Groups A, B, C, and D Class II, Divisions I and II, Groups E, F, G, T5 Class I, Zone 1, AEx d IIC, Ex d IIC, T5 Aluminum / Stainless Steel...
Page 5
,QVWDOODWLRQ Before operation the unit, you must read this user’s Manual thoroughly and retain it for future reference. Before cleaning the unit, you must remove it from the wall or bracket. You must clean it with a wet cloth. Never use liquid cleanser. Enough space must be ensured to installation of this P/T and never rotate PAN/TILT housing forcibly without driving by remote controller.
Page 6
3.1 Wiring 3.1.1 The power box must be installed near EV3000-PT within 20 ft , and the DC24V should be supplied using AWG16 wires. 3-1-2. The built-in receiver address is set to “1” and Baud rate is set to 2400 bps, the unit controlled using any Pelco-D keyboard.
INSTALLATION Conduit Sealing Instructions for Equipment in Hazardous Locations This document is based on NEC installation requirements for equipment installed in hazardous locations in the United States of America. Description Conduit seals prevent explosions from spreading through conduit systems and igniting outside atmospheres. When properly installed and filled with a UL-listed sealing compound, they prevent the passage of gases, vapors, or flames from spreading from a hazardous location to a nonhazardous location.
Page 8
NEC SEC. 501-5 HIGHLIGHTS ON SEALING FITTING REQUIREMENTS CLASS I, DIV. 1 AND 2 Seals must be placed in each conduit of a device that might produce arcs, sparks, or high temperatures. SEC. 501-5(A)(1) PERMITS EXPLOSIONPROOF UNIONS AND ELBOWS BETWEEN SEAL AND 18 MAX APPARATUS...
Page 9
Sealing fittings must be installed at a boundary between a hazardous and nonhazardous area. Sealing fittings must also be installed at a boundary between a Class I, Div. 1 area and a Class I, Div. 2 area. HAZARDOUS AREA NONHAZARDOUS AREA ENCLOSURE TO BE SEALED SEAL MAY BE POSITIONED...