Secure Power SP201 User Manual

Sp200 series
Hide thumbs Also See for SP201:

Advertisement

Secure Power Ltd

User Manual

SP200 Series UPS
SP201
SP202
SP203
Secure Power Ltd
Secure Power Ltd, Unit 3, Bessemer Park, Bessemer Way,
Rotherham, South Yorkshire, S60 1EN.
Email:
sales@secure-power.co.uk
Website:
www.secure-power.co.uk

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SP201 and is the answer not in the manual?

Questions and answers

Summary of Contents for Secure Power SP201

  • Page 1: User Manual

    Secure Power Ltd User Manual SP200 Series UPS SP201 SP202 SP203 Secure Power Ltd Secure Power Ltd, Unit 3, Bessemer Park, Bessemer Way, Rotherham, South Yorkshire, S60 1EN. Email: sales@secure-power.co.uk Website: www.secure-power.co.uk...
  • Page 2 Secure Power Ltd User Manual Secure Power Ltd own the copyright to this document, which may not be copied, reproduced or disclosed to a third party without written permission. Secure Power Ltd reserves the right to make changes in specification without notice or liability. All information is subject to Secure Power Ltd own data and is considered accurate at time of publishing.
  • Page 3: Table Of Contents

    Secure Power Ltd User Manual Contents   Safety ................................5   Warning symbols ............................5   Product description ........................... 6   Applications .............................. 6   Product range ............................6   System block diagram ..........................7   Features ..............................7  ...
  • Page 4 Secure Power Ltd User Manual   Troubleshooting ............................20   Appendix 1 Signals options ........................21   RS232 serial port ............................ 21   USB port ..............................21   SNMP card (advanced monitoring and control) ..................21   Relay card (advanced monitoring and control) ..................22  ...
  • Page 5: Safety

    Safety instructions in this manual are supplementary to local safety instructions. Secure Power Ltd does not accept any liability caused as a result of failure to follow safety instructions. Please note the following: ■...
  • Page 6: Product Description

    Secure Power Ltd User Manual Product description Applications This UPS series provides reliable AC backup power to various types of equipment, for example computer centres, network management centres, auto control systems, and telecommunication systems. Product range The following table lists the models available in the SP200 series. Models with an E suffix are designed for operation with an external battery.
  • Page 7: System Block Diagram

    Secure Power Ltd User Manual System block diagram A functional block diagram representing the UPS is shown in Figure 1. Power is delivered to the output via one of these three paths; a) via the bypass, b) directly through the AC/DC converter and inverter, or c) from the battery via the DC/DC converter and inverter.
  • Page 8: Installation

    Secure Power Ltd User Manual Installation Siting considerations Before unpacking and installing the unit, consider the following: ■ DO NOT expose the UPS to high temperatures, water ingress, flammable or corrosive gas, dust, direct sunlight or explosives. ■ Locate the UPS indoors on a level surface as close as possible to the equipment it will be powering to minimise cable voltage drops.
  • Page 9: Rear Panel Layout

    Secure Power Ltd User Manual Rear panel layout Figure 2 and Figure 3 show the rear panel connections for the two sizes of UPS. Figure 2 Rear panel layout (1 kVA unit) Figure 3 Rear panel layout (2/3 kVA units)
  • Page 10: Unpacking The Ups

    Plug the battery cable into the rear of the UPS (see Figure 2 or Figure 3). 2. Using the supplied cables, connect the UPS output(s) to your load(s). The SP201(E) has three IEC output sockets, and the SP202(E) and SP203(E) have four IEC outputs plus a high current IEC output.
  • Page 11: Operation

    Secure Power Ltd User Manual Operation Working modes The UPS has four distinct modes of operation: ■ On-line mode ■ Bypass mode ■ Battery mode ■ ECO mode Each operating mode is described below. On-Line mode This is the default mode of operation in which the load is supplied via the AC/DC converter and inverter when the a.c.
  • Page 12: Front Panel Controls And Indicators

    Secure Power Ltd User Manual Front panel controls and indicators The front panel controls and indicators are shown in Figure 4. Using the buttons, LEDs and the menu structure displayed on the LCD panel you can: ■ Check the status of the UPS ■...
  • Page 13: Lcd Display

    Secure Power Ltd User Manual LCD display The LCD display comprises a battery capacity graphics section, a fan status section, a charge status section, and a numerical value section as shown below. Loading & battery capacity: number of panes lit indicates the value; top=load,...
  • Page 14: Switching Off The Ups

    Secure Power Ltd User Manual 3. On the front panel, press and hold (see Figure 4 on page 12) until a beep is heard (after approximately half a second). The LEDs flash initially and then the green inverter LED ( ) should be on.
  • Page 15: Eco Mode

    Secure Power Ltd User Manual ECO mode To turn on ECO mode: 1. On the front panel, press for more than 2 s. The following is displayed. characters flash 2. Press for more than 0.5 s but less than 2 s. The following is displayed.
  • Page 16: Output Voltage Level

    Secure Power Ltd User Manual 3. Press for more than 0.5 s but less than 2 s. The following is displayed. characters flash 4. Press for more than 0.5 s but less than 2 s. OFF stops flashing. 5. Press to display ON, which flashes.
  • Page 17: Checking Parameters

    Secure Power Ltd User Manual 4. Press for more than 0.5 s but less than 2 s. OFF stops flashing. 5. Press to display the output voltage you require. The voltages provided are 208 V, 220 V, 230 V (the default value) and 240 V.
  • Page 18: Fault Mode

    Secure Power Ltd User Manual Fault mode In fault mode the UPS cuts off the output or switches to bypass mode, and sounds the buzzer. The warning LED is lit and the display shows a fault code. A list of fault codes is shown on page 27.
  • Page 19: Maintenance

    Secure Power Ltd User Manual Maintenance SP200 series units use sealed lead acid, maintenance free batteries and require minimum maintenance in general. To keep the batteries fully charged and in good condition, ensure the UPS is plugged into the mains at all times. The UPS battery charger guards against over-charging and deep discharge.
  • Page 20: Function Check

    Secure Power Ltd User Manual Function check Perform a self test every 6 months as described on page 14. Troubleshooting Before contacting your distributor, try to solve your problem using the information in the following table. If you need to contact your distributor make sure you have the model number and serial number of your UPS.
  • Page 21: Appendix 1 Signals Options

    Secure Power Ltd User Manual Appendix 1 Signals options RS232 serial port Units are fitted with a standard RS232 serial port, which can be used to: ■ Monitor the UPS power status ■ Monitor the UPS alarm information ■ Monitor the UPS running parameters ■...
  • Page 22: Relay Card (Advanced Monitoring And Control)

    Secure Power Ltd User Manual Relay card (advanced monitoring and control) If your unit has been specified and fitted with the optional relay card (located in the Intelligent Slot on the rear panel) you have access to more advanced monitoring and control functionality via a set of dry contacts and a single opto-coupled input.
  • Page 23 Secure Power Ltd User Manual Opto-coupler input specifications (used for remote shutdown): Parameter Value Reverse voltage (V 6 V d.c. Forward input voltage 30 V d.c. max., 5 to 12 V d.c. typical Forward current 80 mA max., 16 mA typical Pulse forward current (I 1 A (100 µs pulse, 100 pps)
  • Page 24: Appendix 2 Specifications

    SP203, SP203E: 72 V Internal battery type 12 V, 9 AH VRLA maintenance free Backup time SP201, SP202, SP203: > 4 mins. Suffix E backup time is determined by the size of the external battery Charge current SP201, SP202, SP203: 1 A...
  • Page 25: Environment

    Secure Power Ltd User Manual Output Efficiency in battery mode ≥84% Efficiency in ECO mode ≥94% Safety and EMC Safety IEC62040-1 GB4943 Isolation resistance >2 MΩ (500 V d.c.) Isolation voltage 2,820 V d.c., <3.5mA 1 min Conduction: IEC 62040-2...
  • Page 26: Appendix 3 Optional Equipment

    Secure Power Ltd User Manual Appendix 3 Optional equipment The following items are available as options for the UPS: ■ Extension battery box ■ Dry contact relay card ■ SNMP card ■ Battery MCB box ■ Bypass panel …………………………………………………………………………………………………………...
  • Page 27: Appendix 4 Fault Codes

    Secure Power Ltd User Manual Appendix 4 Fault codes Fault Fault code Bus Fault 00 – 19 Inverter Fault 20 – 39 Over Heat 40 – 44 Output short circuit 45 – 49 Overload 50 – 54 Output Relay Fault 55 –...
  • Page 28: Appendix 5 Led Indicator Status

    Secure Power Ltd User Manual Appendix 5 LED indicator status Working status Beeps Comments On-line mode Normal voltage None High/low mains, in battery mode Every 4 s ECO mode Normal voltage None High/low mains, in battery mode Every 4 s...

This manual is also suitable for:

Sp202Sp203

Table of Contents