OPERATING PROCEDURE
4. Removing the compressor
(1)Disconnect the cord connector. (See Phot 5)
(2)Remove the set screws of the relay panel.
(3)Remove the set nuts of the terminal cover.
(4)Pull up the compressor.
(5)Pull out the lead wires from the compressor terminal
to remove overcurrent relay.
(6)Remove set nuts of the compressor base.
(7)Remove the low pressure side welded part and high
pressure side welded part using a burner.
Note:
Before using a welder, release gas inside the unit and
make sure that the gauge pressure shows 0 kg/f.
During welding, open the charge plug because
pressure rises due to expansion by heat
16
PHOTOS
Photo 7
Set nuts of the terminal cover
Photo 8
Nuts
Nuts