8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT

COOL operation

Both indoor and outdoor unit are under the same temperature/
humidity condition.
Operation : TEST RUN OPERATION (Refer to 8-3.)
MUZ-GB50VA
(kgf/
[Gauge])
(MPa [Gauge])
1.0
10
0.9
9
0.8
8
0.7
7
0.6
6
0.5
5
15
18
20
25
50
60
Ambient temperature(°C)
Ambient humidity(%)
NOTE: The unit of pressure has been changed to MPa based on the international system of units (SI unit system).
The conversion factor is: 1 (MPa [Gauge] = 10.2 (Kgf/cm

HEAT operation

Condition :
Dry bulb temperature (°C)
Wet bulb temperature (°C) 14.5
Operation : TEST RUN OPERATION (Refer to 8-3.)
8
7
6
5
4
0
2
5
10
Ambient temperature(°C)
8
7
6
5
4
30
32
35(°C)
15
18
20
25
70
(%)
50
60
Ambient temperature(°C)
Ambient humidity(%)
Indoor
20.0
15
20
25
Dry-bulb temperature (°C)
30
32
35(°C)
70
(%)
[Gauge])
2
Outdoor
2
7
15
20.0
1
6
12
14.5
13
Relative humidity (%)
20
25
30
50
60
70