54 MAINTENANCE
WARNING
The operations described below shall always be
performed with the boiler and the power supply
switched off.
The boiler front panel has to be removed to access the
various devices to be maintained and checked.
1. Push up and pull the front panel forward.
Cleaning the Casing Material
Use a soapy solution and sponge only. Rinse with
clean water and dry with chamois leather or soft cloth.
55 CLEANING THE FLUEWAY
1. Close off the fuel supply to the burner.
2. Ensure that the boiler has been cooled to
ambient temperature.
3. Isolate the mains supply to the boiler and
burner.
4. Disconnect the cable and supply pipe to the
burner.
5. Open the combustion chamber door by
removing the 2 special bolts.
6. Remove the flue way baffles. (Number
variable depending on the model - refer to
Frame 22).
7. Thoroughly clean the flue ways and baffles.
8. Remove the rear cleanout covers and
dispose of the debris/soot that may have
accumulated. (Refer to Frame 29).
9. Replace the rear cleanout covers after first
inspecting and if necessary replacing the
seal. (Refer to Frame 29).
10. Brush out the combustion chamber and
vacuum the soot from beneath the flue ways.
11. Replace the flue baffles into the flue ways.
(Refer to Frame 22 for correct location).
12. Check the condition of the combustion
chamber door insulation.
13. Check the condition of the combustion
chamber door seal.
14. Close the combustion chamber door and
replace the front panel.
15. Re-assemble the burner connections.