AUXILIARY POWER
The RANGER GXT can provide up to 10,000 watts of
120/240 volts AC, single phase 60Hz power for con-
tinuous use, and up to 11,000 watts of 120/240 volts
AC, single phase 60Hz power peak use. The front of
the machine includes three receptacles for connecting
the AC power plugs; one 50 amp 120/240 volt NEMA
14-50R receptacle and two 20 amp 120 volt NEMA 5-
20R receptacles. Output voltage is within +/-10% at all
loads up to rated capacity.
CAUTION
Do not connect any plugs that connect to the
power receptacles in parallel.
------------------------------------------------------------------------
Start the engine and set the "IDLER" control switch to
the desired operating mode. Set the "CONTROL" to
10. Voltage is now correct at the receptacles for auxil-
iary power.
120/240 VOLT DUAL VOLTAGE RECEPTACLE
The 120/240 volt receptacle can supply up to 42 amps
of 240 volt power to a two wire circuit, up to 42 amps
of 120 volts power from each side of a three wire cir-
cuit (up to 84 amps total). Do not connect the 120 volt
circuits in parallel. Current sensing for the automatic
idle feature is only in one leg of the three wire circuit
as shown in the following column.
(Use the shortest length extension cord possible sized per the following table.)
Current
Voltage
Load
Volts
(Amps)
(Watts)
120
15
1800
120
20
2400
240
15
3600
240
20
4800
240
42
10,000
INSTALLATION
RANGER GXT Extension Cord Length Recommendations
Maximum Allowable Cord Length in ft. (m) for Conductor Size
14 AWG
12 AWG
30
(9)
40
(12)
30
(9)
60
(18)
75
(23)
60
(18)
Conductor size is based on maximum 2.0% voltage drop.
RANGER GXT
*Current Sensing for Automatic Idle.
(Receptacle viewed from front of Machine)
120 V DUPLEX RECEPTACLES
The 120V auxiliary power receptacles should only be
used with three wire grounded type plugs or approved
double insulated tools with two wire plugs.
The current rating of any plug used with the system
must be at least equal to the current load through the
associated receptacle.
MOTOR STARTING
Most 1.5 hp AC single phase motors can be started if
there is no load on the motor or other load connected
to the machine, since the full load current rating of a
1.5 hp motor is approximately 20 amperes (10
amperes for 240 volt motors). The motor may be run
at full load when plugged into only one side of the
duplex receptacle. Larger motors through 2 hp can be
run provided the receptacle rating as previously stated
is not exceeded. This may necessitate 240V operation
only.
10 AWG
8 AWG
75
(23)
125
(38)
50
(15)
88
(27)
150
(46)
225
(69)
100
(30)
175
(53)
50
(15)
90
(27)
A-6
GND
120 V
240 V
120 V*
6 AWG
4 AWG
175
(53)
300
(91)
138
(42)
225
(69)
350
(107)
600
(183)
275
(84)
450
(137)
150
(46)
225
(69)