Figure 5-Emergency Call Hook-Up Diagram With; Li381 Corridor Light, Li123B Corridor Light With Buzzer, And Be005 Corridor Bell - TekTone CM800 Operation, Installation And Service Manual

Emergency call signaling system
Table of Contents

Advertisement

Figure 5—Emergency Call Hook-Up Diagram with SF117/4 series Continuous Duty Door Release,

LI381 Corridor Light, LI123B Corridor Light with Buzzer, and BE005 Corridor Bell

TO ADDITIONAL
EMERGENCY
SWITCHES
SF117/4(B,C)
EMERGENCY
SWITCH
Notes:
1. Use 24 VAC connections on SS106 transformer. To calculate cur-
rent requirements, add currents of all devices on at the same time.
Current requirements are as follows:
Corridor Lamp with buzzer– .16 amps
Corridor Bell– .2 amps
Door release– .3 amps
Annunciator lamp– .04 amps
2. Wiring must be #18 gauge except where shown otherwise.
3. BE005 connects to emergency switch on the same floor only.
Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.
RECTIFIER
(See NOTE 9)
+
-
LI123B
LAMP
w/ BUZZER
DOOR RELEASE
SF117/4(B,C)
EMERGENCY
SWITCH
#22
FACTORY CONNECTED
RECTIFIER
(See NOTE 9)
-
+
BE005
CORRIDOR
BELL
LI381
DOME
LAMP
DOOR RELEASE
ANNUNCIATOR LAMPS
TEST BUTTON
NOTE: PM110/4N MODULES ONLY
4. Door release (if used) must be 24 VDC continuous duty type.
5. Switch current capacity is 3 amps.
6. Power supply maximum current is 1 amp.
7. See Figure 4 for additional wiring details.
8. Switches shown in the OFF position.
9. Rectifier RUFO
®
Model 1005 is not available from TekTone
IL514 CM800/CM900 Emergency Call System Manual • 7
TONE
SPEAKER
SS106
24 VAC
TRANSFORMER
(See NOTE 1)
PK2019
117 VAC
R1
R2
TONE
R3
OFF
LAMP
B
TONE
OFF
BUTTON
A
W
S
P
D
N
T1
T2
SS106
16 VAC
TRANSFORMER
117 VAC
®
.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cm900

Table of Contents