TROUBLESHOOTING
1
/15
[]~[] Discharge Gas Temperature Thermistor Abnormality
!
This alarm code is indicated when the thermistor resistance is out of range (Refer below table).
No
Is connector CN24 Td on the
Printed Circuit Board for Relay
Connect correctly
(PCB
) correctly connected?
D
Yes
No
Pull out connector and
measure thermistor resistance.
Replace thermistor
Is resistance correct?
Yes
Check Printed Circuit Board
Thermistor
resistance
(KΩ)
Air temperature (°C)
Thermistor for Discharge Gas Temperature
characteristics