Position
Position of the flue terminal
Horizontal flues
directly below an opening, air brick,
A
opening windows
B
above an opening, air brick, opening windows
horizontally to an opening, air brick, opening
C
windows
D
below gutter, drain/soil pipe
E
below eaves
F
below a balcony or car port
G
from vertical drain pipes and soil pipes
H
from internal/external corners
H
to a boundary alongside the terminal
(2)
I
above adjacent ground or balcony level
J
from surface or a boundary facing the terminal
(2)
0020107232_00 - 02/11 - Glow-worm
mm
Position
Position of the flue terminal
from opening (door/window) in car port
L
into dwelling
300
M
vertical from a terminal
300
N
horizontally from a terminal
Vertical flues
300
P
from another terminal
25
Q
above roof level
25
(1)
R
from adjacent opening window
25
S
from adjacent wall to flue
25
25
(1) There should be no ventilation/opening in the eaves within
300
300mm distance of the terminal.
300
(2) These dimensions comply with the building regulations,
600
but they may need to be increased to avoid wall staining and
nuisance from pluming depending on site conditions.
INSTALLATION
Diagram 4.2
mm
1200
1500
300
600
300
1000
300
- 11 -