Gas Piping; Electrical Controls And Wiring; Boiler Room Air Supply And Ventilation - Slant/Fin SENTINEL SE-70 Installation And Operating Instructions Manual

Hide thumbs Also See for SENTINEL SE-70:
Table of Contents

Advertisement

Sentinel

GAS PIPING

A. Local installation codes apply. The pipe joint compound
used on threads must be resistant to the action of liquefied
petroleum gases.
B. The gas supply line to the boiler should be run directly from
the meter for natural gas or from the fuel tank for L.P .
propane gas. See page 2 for location of union and manual
main shutoff valve that may be specified locally.
Selecting pipe size for natural gas:
1. Measure or estimate the length of piping from the meter
to the installation site.
2. Consult gas supplier for heating value of gas-W/m
(BTU/cu. ft.).
3. Divide boiler rated input by heating value to find gas flow
in piping (m
/hr) (cu. ft. per hour).
3
4. Use table below to select proper pipe size.
Example: Boiler model SE-175 is to be installed. Distance
from gas meter to the boiler is 6.1m (20 ft). Heating value of
natural gas is 10560 W/m
pipe size.
51 290 W/hr
Gas flow =
10 560 W/m
175,000 BTU/hour
(
Gas flow =
1020 BTU/cu. ft.
At 6.1m (20 ft.) length of pipe, match required capacity from
table below (choose higher capacity, in this case is 5.4 m
[190 cu. ft.] per hour). Required pipe size is 19mm (3/4").
Improper gas pipe sizing will result in pilot flame outages,
insufficient heat and other installation difficulties. For more
information and also if other appliances are to be attached
to the piping system, see Appendix C of National Fuel Gas
Code ANSI Z223.1-latest edition or CSA B149.1-00 for nat-
ural gas and propane.
C. The boiler and its gas connection must be leak tested before
placing the boiler in operation. Use liquid soap solution for
all gas leak testing. Do not use open flame.
This boiler and its individual shutoff valve must be discon-
nected from the gas supply piping system during any pres-
sure testing of that system at test pressures in excess of
3.5 kPa (1/2 PSIG). This boiler must be isolated from the gas
supply piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than 3.5 kPa (1/2
PSIG).
Length
Pressure Drop = 8mm (.3") in water Specific Gravity = 0.60
of Pipe
Iron Pipe Size (Ips)—inches
13mm (1/2")
19mm (3/4")
m
ft
m
/hr cu.ft./hr. m
/hr cu.ft./hr. m
3
3
3.0
10
3.7 132
7.9 278
6.1
20
2.6
92
5.4 190
9.1
30
2.1
73
4.3 152
12.2
40
1.8
63
3.7 130
15.2
50
1.6
56
3.3 115
18.3
60
1.4
50
3.0 105
21.3
70
1.3
46
2.7
24.3
80
1.2
43
2.5
27.4
90
1.1
40
2.4
30.5 100
1.1
38
2.2
At pressure drop of 0.3 in. water, specific gravity = 0.60.
(1020 BTU/cu. ft.) Select proper
3
= 4.9 m
/hr
3
3
= 171.5 cu. ft. per hour
Gas Flow In Piping
25mm (1")
32mm (1-1/4") 38mm (1-1/2")
/hr cu.ft./hr. m
/hr cu.ft./hr. m
3
3
3
14.7 520
29.7 1050
45.3 1600
9.9 350
20.7 730
31.1 1100
8.1 285
16.7 590
25.2 890
6.9 245
14.2 500
21.5 760
6.1 215
12.5 440
19.0 670
5.5 195
11.3 400
17.3 610
96
5.1 180
10.5 370
15.9 560
90
4.8 170
9.9 350
15.0 530
84
4.5 160
9.1 320
13.9 490
79
4.2 150
8.6 305
13.0 460
D. All gas piping used should be inspected thoroughly for
cleanliness before makeup. A sediment trap must be pro-
vided, as illustrated on page 2.
E. The minimum and maximum gas supply pressure (at the
inlet of gas valve) are shown on the boiler rating plate for the
type of gas used. Gas supply pressure should never be less
than minimum or more than maximum pressure when the
boiler or any other appliance is turned on or off.

ELECTRICAL CONTROLS AND WIRING

A. The electrical power to the boiler must be on a separately
fused and live circuit.
3
B. If an external electrical source is utilized, the boiler, when
installed, must be electrically grounded in accordance with
the requirements of the authority having jurisdiction or, in
absence of such requirements, with the Canadian Electric
Code – CSA-C22.1, Part 1 – latest edition.
C. Basic control wiring diagrams are supplied. Other control
systems may be factory supplied, see User's Information
Manual and Instructions packed with control system sup-
plied.
D. After placing the boiler in operation, the safety shutoff device
must be tested. See page 12 safety check.
)

BOILER ROOM AIR SUPPLY AND VENTILATION

An ample supply of air is required to obtain combustion and
ventilation. ALL AIR COMES FROM OUTSIDE, directly through
3
wall openings to the boiler or through unsealed openings
around windows, doors, etc. in the whole building. When build-
ings are insulated, caulked and weather stripped, now or later
on, direct openings to outside may be required and should be
provided. If the boiler is not near an outside wall, air may be
ducted to it from outside wall openings.
Provisions for combustion and ventilation air must be made in
accordance with section 5.3, Air for Combustion and Ventila-
tion, of the National Fuel Gas Code, ANSI Z223.1-latest edition
or CSA B149.1-00 for natural gas and propane, or applicable
provisions of the local building codes. The following recom-
mendation applies to buildings of energy-saving construction,
fully caulked and weather stripped:
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES
TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR
INTO THE BOILER ROOM:
1. Air drawn horizontally from outdoors DIRECTLY through an out-
side wall; one louvered opening near the floor and one louvered
opening near the ceiling, each opening with a minimum FREE air
passage area of 550 mm2 per kW (1 square inch per 4000 BTUH)
of total appliances' input.
2. Air drawn horizontally through HORIZONTAL DUCTS; one open-
ing near the floor and one opening near the ceiling, each opening
/hr cu.ft./hr.
with a minimum FREE air passage area of 1100 mm2 per kW (1
square inch per 2000 BTUH) of total appliances' input.
3. Air drawn VERTICALLY from outdoors; one opening at the floor
and one opening at the ceiling, each opening with a minimum
FREE air passage area of 550 mm2 per kW (1 square inch per
4000 BTUH) of total appliances' input.
4. Air drawn from inside the building; one opening near the floor and
one opening near the ceiling, each opening with a minimum
FREE air passage area of 2200 mm2 per kW (1 square inch per
1000 BTUH) of total appliances' input.
7

Advertisement

Table of Contents
loading

Table of Contents