SERVICE MANUAL
Model: HA10TG20SW/S/B
.
5-3.Defrosting Principle
1. A defrost cycle will start after an accumulated compressor run time of 4 hours.
2. Automatic Defrost
2.1 It could enter defrost after an accumulated compressor run time of 3~48 hours according to
ambinet temperature,door open–close
2.2 It will stop defrosting when defrost sensor temperature reach 12℃or the defrost time is up to
50 munutes.
2.3 If the defrost time does not reach 50 minutes,but the temperature reaches 12 ℃,the defrost
will be stopped immediately.
3. Rated defrost heater power :150W.
Note: It must be in rated voltage 115V/60Hz, above parameters is practical.
5-4. Sensor location
Issue
2009-7-24
Rev. Ref0907S005V0
17