Alignment and Adjustments
3-1-2 Wired Remocon Error Display
Display
3-4
Explanation
Indoor unit Communication Error
Indoor/Outdoor unit Communication Time Out Error
60 Packet Over data
Indoor unit is not connected
Communication Error between Outdoor Main and Inverter Micom
(Occurred after 1 minute detection in Main and Inverter)
Indoor Temp. Sensor(OPEN/SHORT ERROR)
Indoor Unit Eva in sensor(OPEN/SHORT ERROR)
Indoor Unit Eva in sensor Separation
Outdoor Temp. Sensor Error(OPEN/SHORT ERROR)
COND Temp. Sensor Error(OPEN/SHORT ERROR)
Inverter Compressor Discharge Temp. sensor Error(OPEN/SHORT ERROR)
Indoor Float S/W 2
Detection
nd
Outdoor unit-Indoor unit Communication wire Voltage Detection
Outdoor unit Refrigerant Full Leakage(Gas Leak)
Outdoor door Fan Error
[Inverter]Inverter Compressor Start Failure
[Inverter]DC PEAK Error
[Inverter]DC LINK Voltage 150V below, 410V Over
[Inverter]Compressor Rotation Error
[Inverter]Current Sensor Error
[Inverter]DC LINK Sensor Error
[Inverter]EEPROM READ/WRITE Error
[Inverter]Inverter ZERO CROSSING Error
Outdoor unit Capacity Setup Option Error
Wired Liquid Crystal ↔ Indoor unit Comm. Error
Master Wired Liquid Crystal ↔ Slave Liquid Crystal Comm. Error
Wired Liquid Crystal COM1/COM2 Cross Error
Error of setting option for wired remote controller COM2
Remark
Communication ERROR
INDOOR SENSOR ERROR
OUTDOOR SENSOR ERROR
SELF DIAGNOSYS ERROR
OUTDOOR UNIT PROTECTION
CONTROL ERROR
WIRED REMOTE CONTROL ERROR