15 Fault Finding
15 Fault finding
Logical fault finding procedure
These checks must be carried out before attempting to
use the fault finding guide.
1. Carry out electrical safety checks (see section
'preliminary electrical checks' 13.1)
2. Check that the external electricity supply to the boiler
is on, and a supply of 230V is present at the boiler
terminal strip
3. Check that the gas supply to the boiler is on, that it
has been correctly purged and that an inlet pressure
of 20mbar is available at the gas valve (see section
'gas supply' 13.3)
code
description
F1
Ignition fault (lockout)
Failed to light
F4
Ignition fault (lockout)
Went out when lit
F5
Overheat fault
F6
Central heating flow NTC fault
F10
Central heating return NTC fault
F11
No reception by main board
F12
No reception by the local user interface
F13
Main board fault
F14
Central heating flow t° > 95° C
F16
Flame detection fault
(flame presence >5 s after burner stop)
F17
Power supply <170 V
F18
Local user interface fault
F19
Central heating NTC unplugged
F20
MMI software incompatible with IRIS software Possible connection fault
F24
Central heating return t° >90°C
F25
Maximum temperature rise slope
F26
Maximum delta t
26
4. Ensure the heating system is full of water and
charged to between 1 and 1.5 bar, on sealed systems
5. Check that the main on/off control is set to the 'on'
position
6. Set the central heating temperature to maximum
7. Check that all external controls are on and calling for
heat
8. Check that all manual circuit controls ie. bypass,
radiator valves are correctly adjusted
Fault codes
Fault codes take priority over all other display functions
in the event of a system fault occurring.
comment
No gas; Insufficient gas; Incorrect gas valve adjustment; Electrode defect;
Ignition lead defect; Electronic igniter defective; Check air inlet duct;
Check connections to igniter unit
As above
Overheat stat operated; Maximum temperature exceeded;
Check thermistor connections; Air in system with thermistor at maximum
setting; Faulty overheat stat connection; Check that pump is wired into
appliance and not from programmer. This would cause no pump overrun
Flow NTC cable defective/broken NTC faulty
Flow thermistor not fitted correctly
Return NTC cable defective/broken NTC faulty
Check that thermistor attached correctly to pipe.
Connection fault between main PCB and interface; Faulty interface;
Faulty main PCB (processor)
As F.11
As F.11
System fault; Possible external pump failure; Check NTC on flow
Check that pump is wired into appliance and not from programmer.
This would cause no pump overrun
Gas valve defective
Check electrical supply / polarity
Connections; Faulty interface
Check NTC connection
System fault; Possible external pump failure; Check NTC on return;
Check that pump is wired into appliance and not from programmer.
This would cause no pump overrun.
Possible external pump failure; Air in system restricting movement of water.
Insufficient circuit flow
Check NTC on return; System fault – too restrictive?; Possible pump failure