Dimensions, clearance and plumbing connections

Dimensions, clearance and plumbing connections

Optima

Left-hand side
1190
640
Required installation space for the heat pump.
Minimum distance from the pump to the wall is 300 mm.
Minimum distance in front of the pump 1000 mm, to the sides 500 mm.
If a roof is installed it must be positioned at least 1.5 m above the heat
pump to avoid the recirculation of cold air.

290 A/W

Required installation space for the electric boiler.
A free space of 600 mm is required in front of the electric boiler. The other
sides can be blocked.
A minimum of 25 mm is required between the electric boiler and other
permanent installations (walls, sinks, etc.). A suitable placement is against
an outer wall or insulated partition wall.
Front
60
820
12
Back
Drainage
Electric lead-ins
1) To the electric boiler
(Cu 28).
(Connect to 1) in the elec-
tric boiler picture.
2)
From the electric boiler
(Cu 28).
(Connect to 2) in the
electric boiler picture.
105
220
411
290 A/W
Min. 25 mm
Min. 600 mm
Wall
Front
Min. space 1,240 mm
Insu-
lated
wall