[For Half-Concealed Installation]
Suspension-bolt pitch should be as shown in the figure.
40
Ceiling Opening: 1580
Ceiling Opening: 640
INDOOR UNIT
3.3.4. Select piping direction
Select connection piping and drain piping directions.
4 Left rear piping
5 Left piping
(Drain pipe only)
(Drain pipe only)
INDOOR UNIT (TOP VIEW)
[FOR ○
Left rear piping, ○
4
Transfer the Drain cap and Drain cap seal.
Drain Cap seal
3.3.5. Drilling the holes and attaching the suspen-
sion bolts
(1)
Drill ø25 mm holes at the suspension-bolt locations.
(2)
Install the bolts, then temporarily attach Special nuts A and
B and a normal M10 nut to each bolt. (The two special
nuts are provided with the unit. The M10 nut must be
obtained locally.) Refer to the figure.
Bolt Strength [N (kgf)]
Ceiling panel
Special nut A (Included)
10 to 15
Special nut B (Included)
M10 Nut (Obtained locally)
40
Ceiling panel
15
Ceiling panel
Suspension bolt should
extend outward 30 to 50 mm.
2 Top piping
(Connection pipe only)
1 Right rear piping
3 Right
piping
Cut off the piping outlet cutting groove
with a hacksaw, etc.
Left piping]
5
Drain Cap
Indoor Unit
Drain Pan
Drain Cap Seal
Drain Cap
Push cap all the way on
(as far as it will go).
980 to 1470 (100 to 150)
Unit : mm
www.enindel.com
3.3.6. Installing the indoor unit
(1)
Lift unit so that suspension bolts pass through the suspen-
sion fittings at the sides (four places), and slide the unit
back.
Unit : mm
(2)
Fasten the indoor unit into place by tightening-up the
special "B" bolts and the M10 nuts. Make sure that unit is
secure and will not shift back and forth.
[For Half-Concealed Installation]
When installing the indoor unit in a semi-concealed orienta-
tion, make sure to reinforce the insulation of the unit on all
sides. Drops of water may fall from the unit if it is not thor-
oughly insulated.
In order to check the drainage, be sure to use a level dur-
ing installation of the indoor unit. If the installation site of
the indoor unit is not level, water leakage may occur.
Ceiling
Ceiling panel
INDOOR UNIT
Glass wool insulate
(10 to 20 mm thick)
INDOOR UNIT
(TOP VIEW)
CAUTION
Wall
Wall
Wall
Ceiling panel
En-5