8.2. Function setting

STEP 2
Selecting the Function Number and Setting Value
(1)
Press the SET TEMP. (
tion number. (Press the MODE button to switch between
the left and right digits.)
(2)
Press the FAN button to proceed to setting the value.
(Press the FAN button again to return to the function
number selection.)
(3)
Press the SET TEMP. (
ting value. (Press the MODE button to switch between the
left and right digits.)
(4)
Press the TIMER MODE button, and START/STOP button,
in the order listed to confirm the settings.
(5)
Press the RESET button to cancel the function setting
mode.
(6)
After completing the FUNCTION SETTING, be sure to turn
off the power and turn it on again.
Function number
After turning off the power, wait 10 seconds or more before
turning on it again. The FUNCTION SETTING doesn't
become effective if it doesn't do so.
Setting the Ceiling Height
Select the setting values in the table below according to the
height of the ceiling. (The unit is factory-set to "00".)
Setting Description [m] Function Number
Standard
(2.5 to 3.0)
High ceiling
(3.0 to or more)
Setting the Filter Sign
The indoor unit has a sign to inform the user that it is time to
clean the filter.
Select the time setting for the filter sign display interval in the
table below according to the amount of dust or debris in the
room. (The unit is factory-set to "00".)
If you do not wish the filter sign to be displayed, select the
setting value for "No indication".
Setting Description
[hours]
Standard
(2,500)
Long interval
(4,400)
Short interval
(1,250)
No indication
En-12
) (
) buttons to select the func-
) (
) buttons to select the set-
Setting value
CAUTION
Setting Value
20
Function Number
Setting Value
11
www.enindel.com
Setting the Cooler Room Temperature Correction
Depending on the installed environment, the room tempera-
ture sensor may require a correction. The settings may be
selected as shown in the table below. (The unit is factory-set
to "00".)
Setting Description
Standard
Lower control
Setting the Heater Room Temperature Correction
Depending on the installed environment, the room tempera-
ture sensor may require a correction. The settings may be
changed as shown in the table below. (The unit is factory-
set to "00".)
Setting Description
Standard
Lower control
Slightly warmer control
Warmer control
Setting Other Functions
The following settings are also possible, depending on the
operating conditions. (The unit is factory-set to "00".)
Auto Restart
Setting Description
Indoor Room Temperature Sensor Switching Function
(Wired remote controller only)
Setting Description
If setting value is "00", room temperature is controlled by the
indoor unit temperature sensor.
If setting value is "01", room temperature is controlled by
either indoor unit temperature sensor or remote control unit
sensor.
00
Setting record
01
Record any changes to the settings in the following table.
Ceiling height
Filter sign
Cooler room temperature
correction
Heater room temperature
correction
Auto restart
00
Indoor room temperature
sensor switching function
01
After completing the FUNCTION SETTING, be sure to turn off
the power and turn it on again.
02
03
Function Number
30
Function Number
31
Function Number
Yes
40
No
Function Number
No
42
Yes
Setting
Setting Value
00
01
Setting Value
00
01
02
03
Setting Value
00
01
Setting Value
00
01
Setting Value