6-2. Optional Auxiliary Power Receptacles

6-3. Wiring Optional 240 Volt Plug

Current Available in Amperes
240 V
Each 120 V Duplex
Receptacle*
Receptacle
35
30
25
20
15
V x A = Watts
*One 240 V load or two 120 V loads.
OM-945 Page 20
7
0
5
10
15
20
1
3
4
120V
120V
240V
6
2
3
4
240V
6
5
Y If unit does not have GFCI re-
ceptacles,
use
protected extension cord.
Combined output of all receptacles
limited to 10 kVA/kW rating of the
generator.
GFCI Receptacle Option
1
120 V 20 A AC GFCI Recep-
tacles GFCI2 and GFCI3
GFCI2 and GFCI3 supply 60 Hz
single-phase power at weld/power
1
speed. Maximum output from
GFCI2 or GFCI3 is 2.4 kVA/kW. Cir-
cuit breaker protection is the same
as standard receptacles.
If a ground fault is detected, the
GFCI Reset button pops out and
the circuit opens to disconnect the
faulty
equipment.
Check
damaged tools, cords, plugs, etc.
connected to the receptacle. Press
button to reset receptacle and
resume operation.
.
At least once a month, run
engine at weld/power speed
and press Test button to verify
GFCI is working properly.
The plug can be wired for a 240 V,
2-wire load or a 120/240V, 3-wire
load. See circuit diagram.
1
Plug Wired for 120/240 V,
3-Wire Load
When wired for 120 V loads, each
duplex receptacle shares a load
with one half of 240 V receptacle.
2
Plug Wired for 240 V, 2-Wire
5
Load
3
Neutral (Silver) Terminal
4
Load 1 (Brass)Terminal
5
Load 2 (Brass) Terminal
6
Ground (Green) Terminal
7
Amperes Available Using
120/240 V Plug
Tools Needed:
GFCI-
for
120 813-D