angle and facilitate repositioning to the original setting
after having moved the floodlight for servicing. Also, a
sight has been cast into the top of the housing as an aid in
aiming the unit during daylight hours.
PHOTOELECTRIC CONTROL
Photoelectric control receptacle (if present) should be
oriented before control is installed. Loosen the two
holding screws and rotate receptacle until "North" is
directed as near as possible to true north. Tighten
holding screws and install control.
WIRING
Make all electrical connections in accordance with
the National Electrical Code and any applicable
local code requirements.
Verify that supply voltage is correct by comparing
it to nameplate.
If unit is designated as multivolt or multiwatt,
follow specific instruction.
Connect ground lead to the green lead, green
ground screw on housing or terminal block
provided.
Do not remove insulated connectors from wires
not needed for required voltage connection.
When changing voltage on reconnectable units,
move only the lead with the insulated connector.
IF SINGLE VOLTAGE:
All single voltage ballasts are pre-wired such that
user need only connect the supply conductors.
IF MULTIVOLT: (120/208/240/277 volts)
Connect the ballast lead with the insulated termi-
nal to the desired voltage terminal as indicated on
the ballast terminal nameplate.
IF MULTIWATT:
Multiwatt ballasts are available in various combi-
nations of wattage. See wiring instructions on
wiring tag inside the luminaire.
TRUNNION MOUNTED LUMINAIRES — Three-
conductor No. 14 cable (with 90°C minimum insulation)
is recommended for making electrical connections to
these units. Open the floodlight by loosening two screws
"B" and pulling the door forward. Remove the insulation
shield from the reflector to expose the wiring entrance
and terminal board. Loosen screws in pressure plate,
insert cable through grommet, and retighten screws.
(Notice that grommet fits cable of approximately 9/16-
inch diameter.) Grommet and pressure plate form a
weatherproof seal and strain relief. To maintain this
seal, screws in pressure plate must be retightened
g
GE Lighting Solutions • 1-888-MY-GE-LED • www.gelightingsolutions.com
GE Lighting Solutions is a subsidiary of the General Electric Company. Evolve and other trademarks belong to GE Lighting Solutions. The GE brand and logo are trademarks of the General Electric Company.
© 2011 GE Lighting Solutions. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions.
whenever seal is disturbed.
Connect line lead to first (#1) terminal board position
and neutral lead to last (#3) position and connect
ground lead to the terminal with the green lead attached.
Before closing luminaire, be sure insulation shield is
properly attached to the reflector.
SLIPFITTER-MOUNTED AND WALL-MOUNTED UNITS —
Splice supply leads to three leads inside wiring box.
Splice line lead to black lead, neutral lead to white lead,
and ground lead to green lead, which is electrically
connected to floodlight housing.
L A M P S
Use only lamps specified on nameplate. Observe
lamp manufacturer's recommendations and
restrictions on lamp operation, particularly ballast
type, burning position, etc.
The VLU is designed for high pressure soduim (HPS),
"Deluxe White" mercury, and metal halide lamps of 400
watts and less, depending upon the ballast installed. The
HLU is designed for HPS lamps only.
Lamp Tightness – Mogul Base Lamp: The lamp
should be securely inserted to the NEMA-EEI specified
torque of 35 inch-pounds, which is best achieved by
very firmly tightening to insure application of sufficient
torque. Tightening must be sufficient to fully depress
and load the center contact of the socket.
MAINTENANCE
This unit has a ballast tray which can be removed
for easy replacement of the ballast, ignitor or capacitor.
To remove the tray, disconnect the supply leads from
the terminal board, separate the disconnect to the
lamp and photoelectric control, loosen the screws at
the top of the ballast tray and slide the tray to the
left so that the tray can be pulled free over the
keyhole slots. Reverse this procedure for installation.
The ALGLAS
be cleaned with any suitable non-abrasive glass cleaning
solution, soap or detergent, and rinsed with clean water.
1
- 8 8 8
-
6 9
-
4 3 5 3 3
-
CAUTION
Risk of burn
• Allow lamp/fixture to cool before
handling
WARNING
Risk of burn
• Do not touch operating luminaire
®
finished reflector and door glass may
35-201578-65 (1/00)