Heat Transfer MODCON VWH 300 LP Installation & Maintenance page 33

Gas-fired hot water supply boiler
Table of Contents

Advertisement

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL
Fig. 6-1
CAUTION
The condensate line must remain unobstructed,
allowing free flow of condensate. If condensate
is allowed to freeze in the line or if the line is
obstructed in any other manor, condensate can
exit from the boiler tee, resulting in potential
water damage to property.
GAS-FIRED HOT WATER SUPPLY BOILER
3/4" SWEAT PVC
PIPING/FITTINGS
PIPE HANGER
ASSEMBLIES FOR
SUPPORT
CONDENSATE PUMP
CONDENSATE
HORIZONTAL LINES MUST BE INSTALLED
WITH A PITCH OF 1/4" PER FOOT
Fig. 6-2
When servicing is complete, you must
make sure the cap is replaced securely.
Failure to do so will cause venting issue
that will result in serious injury or death.
NEUTRALIZER
PIPE SUPPORT
CLEAN OUT PORT
When installing a condensate pump, select one
approved for use with condensing boilers and
furnaces. The pump should have an overflow
switch to prevent property damage from
condensate spillage.
Condensate from the Mod Con Boiler will be
slightly acidic (typically with a pH from 3.2 to
4.5). Install a neutralizing filter if required by
local codes.
Boiler Manual
(CONTINUED)
CONDENSATE
OVERFLOW SWITCH
NOTE: TO CLEAN OUT CONDENSATE
COLLECTOR ;USE A WET VAC INSIDE
THE OPEN PORT TO THE CONDENSATE
COLLECTOR. THIS WILL HELP REMOVE
ANY FOREIGN MATTER THAT MAY BLOCK
THE CONDENSATE LINE.
CONDENSATE CAP
n
WARNING
LP-205-ZZ Rev. 2/19/09
CONDENSATE NEUTRALIZER
WITH PUMP
3/4" SWEAT PVC TEE
OPEN TO ATMOSPHERE
LP-205-W Rev. 5/14/08
NOTICE
32