Service Valve
Valve Closed
Valve Open
Figure 10
To Open Liquid or Suction Line Service Valve:
1. Remove stem cap with an adjustable wrench.
2. Use a service wrench with a hex-head extension to back
the stem out counterclockwise as far as it will go. Use a
3/16" hex head extension for liquid line service valves
and a 5/16" extension for suction line service valves.
3. Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
To Close Liquid or Suction Line Service Valve:
1. Remove the stem cap with an adjustable wrench.
2. Use a service wrench with a hex-head extension to turn
the stem clockwise to seat the valve. Tighten firmly.
3. Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
Suction Line (Ball Type) Service Valve
Suction line (ball type) service valves function the same way
as the other valves; the difference is in the construction (see
Figure 11).
Page 10 of 24
The ball valve is equipped with a service port with a factory-
installed Schrader valve. A service port cap protects the
Schrader valve from contamination and serves as the primary
seal.
Leak Testing
After the line set has been connected to the indoor and
outdoor units, the line set connections and indoor unit must
be checked for leaks.
Using an Electronic Leak Detector
1. Connect the high pressure hose of the manifold gauge
set to the suction valve service port. (Normally the high
pressure hose is connected to the liquid line port;
Use adjustable wrench. To open, rotate stem
counterclockwise 1/4 turn (90°). To close, rotate
stem clockwise 1/4 turn (90°).
however, connecting it to the suction ports helps to
protect the manifold gauge set from damage caused
by high pressure.)
2. With both manifold valves closed, connect the cylinder
of R-410A refrigerant. Open the valve on the R-410A
cylinder (vapor only).
3. Open the high pressure side of the manifold to allow
R410A into the line set and indoor unit. Weigh in a trace
amount of R-410A. (A trace amount is a maximum of 2
oz. of refrigerant or 3 lbs. pressure.) Close the valve on
the R-410A cylinder and the valve on the high pressure
side of the manifold gauge set. Disconnect the R410A
cylinder.
Issue 1143
Ball Type Service Valve
(Valve Open)
Figure 11
506762-01