Draft Regulators; Duct Work/Air Conditioning/Supply/Return Airflow And Air Temperature - Thermo Products Spirit VHF-ABE Installation, Operation And Service Manual

Oil-fired central furnace
Table of Contents

Advertisement

All installations and services must be performed by qualified service personnel.
SIDE WALL VENTING APPLICATION ORDER INFORMATION
FIELD VENT TERMINATION
BURNER
(15' application MAX)
Beckett AFG
Beckett NX
The Field vent kit is set up with 4 inch diameter vent pipe with concentric through-the-wall vent termination/inlet air
vent hood. The combustion air inlet pipe diameter is also 4 inch diameter. For Beckett, the combustion air inlet pipe
will be reduced to 3" diameter with the Beckett side wall vent kit.
The side wall vent may be installed either through the upper knock-out on the left side casing of the unit or vertically
out the top opening of the vestibule. The 4" flexible vent pipe included w/ Field vent kit is able to be installed at 2"
clearance to combustibles.
The combustion air inlet can be installed through the either the lower left side casing knock-out or the lower right
side casing knock-out.
B. DRAFT REGULATORS:
A draft regulator is supplied with the furnace and should be installed according to the regulator manufacturers
recommendations. With the burner operating, use a draft gauge to adjust the regulator to the proper setting. (refer to
the instructions enclosed with draft regulator to adjust to the proper setting). When the burner air supply and draft are
properly adjusted, the overfire draft should be a negative (-).01" to (-).02" WC
air tap (See Fig. 4). This tap is provided in the upper burner mounting plate. To measure the flue draft, punch a small
hole in the vent connector pipe as close to the furnace as possible and always before the draft regulator.
Note:
1. Draft overfire may be positive for high fire applications but not to exceed (+).02" WC.
C. DUCT WORK/AIR CONDITIONING/SUPPLY/RETURN AIRFLOW AND AIR TEMPERATURE:
If the furnace is used in connection with summer air conditioning (cooling), the furnace should be installed parallel
with or on the upstream side of the evaporator coil to avoid condensation in the furnace heat exchanger. If the
cooling unit is installed with a parallel flow arrangement, dampers or other means used to control flow of air should
be provided to prevent chilled air from entering the furnace. If such a damper is manually operated, it must be
equipped with a means to prevent operation of either unit, unless the damper is in the full heat or cool position.
The supply/return airflow shall be set to obtain an air temperature rise, across the furnace, in the range of 55º to
85ºF. Since the flow resistance of each duct system is slightly different, the airflow (fan speed) may have to be
changed in the field to achieve a satisfactory temperature rise.
One way to measure the temperature rise across the furnace is to insert temperature measuring devices (e.g.
thermometers) into the return air duct and into the supply air duct about 12 inches from the furnace. After the furnace
has been firing continually for over 20 minutes, read the temperature difference between the two (2) thermometers.
The temperature difference should not exceed 85ºF, nor be less than 55ºF. A temperature rise of 70ºF is considered
to be optimum for comfort.
The blower (fan) speed fan is adjusted by changing the fan motor winding energized by the control system. The
furnace is set on fan speed, "ML", at the factory, refer to page 13 of this manual. To adjust the fan speed, change
corresponding wire from the appropriate fan speed to the "HEAT" tap on the control.
KIT
PART NUMBER
AOPS8393
AOPS8393
SIDE WALL VENT
COMBUSTION AIR INTAKE
ACCESSORIES KIT
(BURNER SPECIFIC)
PART NUMBER
AOPS8394
AOPS8412
1
, as measured at the 5/16" overfire
3
HOOD KIT
(FOR COMBUSTION AIR
APPLICATIONS ONLY)
PART NUMBER
AOPS8397
AOPS8413

Advertisement

Table of Contents
loading

This manual is also suitable for:

Spirit vhf-abpSpirit vhf-aneSpirit vhf-anp

Table of Contents