Lennox Hearth Products Electronic LMDV-3530-CNM Installation Instructions Manual page 15

Direct vent merit lmdv-33/35/40 series vented gas fireplace heaters
Table of Contents

Advertisement

Notes:
• It is very important that the horizontal/in-
clined run be maintained in a straight (no
dips) and recommended to be in a slightly
elevated plane, in a direction away from the
fireplace of 1/4" rise per foot (20 mm per
meter) which is ideal, though rise per foot
run ratios that are smaller are acceptable all
the way down to at or near level.
• SV4.5VF (Secure Vent), SF4.5VF (Secure
Flex) firestop/spacer must be used anytime
vent pipe passes through a combustible
floor or ceiling. SV4.5HF (Secure Vent),
SF4.5HF (Secure Flex)firestop/spacer must
be used anytime vent pipe passes through
a combustible wall.
• Two 45 degree elbows may be used in place
of one 90 degree elbow. The same rise to
run ratios, as shown in the venting Figures
for 90 elbows, must be followed if 45 degree
elbows are used.
• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF
VERTICAL RISE EXCEPT WHERE AN ELBOW
IS THE ONLY VERTICAL COMPONENT IN
THE SYSTEM (See Figure 37).
u
Ceiling Firestop /
(12.2 meters)
Spacer (SV4.5VF)
u
When using Secure Flex, use Firestop / Spacer
SF4.5VF
A Vent Restrictor, as shown in Figure 18
Page 11, must be used in this application
Figure 28
- Top Vent - STRAIGHT
H Maximum
feet
2
4
6
8
V + H = 40 feet (12.2 meters) Max.
H = 8 feet (2.4 meters) Max.
Example: If 8 feet of (H) horizontal vent run
is needed, then 4 feet minimum (V) vertical
vent will be required.
This table shows a 1(V) to 2(H) ratio. For
every 1 foot of (V) vertical, you are allowed 2
feet of (H) horizontal run, up to a maximum
horizontal run of 8 feet.
Figure 29
40 feet
Maximum
V1
u
W hen using Secure Flex, use Firestop /
Spacer SF4.5VF.
v
W hen using Secure Flex, use Firestop /
Spacer SF4.5HF.
Figure 30
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Table A
V Minimum
(meter)
feet
(meter)
(0.610)
1
(0.305)
(1.219)
2
(0.610)
(1.829)
3
(0.914)
(2.438)
4
(1.219)
Ratio V to H ratio is 1:2
- Rear Vent - ONE 90 DEGREE ELBOW
H
u
Ceiling Firestop /
Spacer (SV4.5VF)
v
Wall Firestop/
Spacer (SV4.5HF)
- Top Vent - TWO 90 DEGREE ELBOWS
u
When using Secure Flex, use Firestop /
Spacer SF4.5VF.
u
Ceiling Firestop /
Spacer (SV4.5VF)
V
H
Table B
H Maximum
feet
(meter)
feet
5
(1.524)
5
(1.524)
1
10
(3.048)
2
15
(4.572)
3
20
(6.096)
4
V + V
+ H = 40 feet (12.2 m) Max.
1
H = 20 feet (6.096 meters) Max.
V
Example: If 20 feet of (H) horizontal vent run
is needed, then 4 feet minimum of (V) vertical
vent will be required.
This table shows a 1(V) to 5(H) ratio. For
every 1 foot of (V) vertical, you are allowed 5
feet of (H) horizontal run, up to a maximum
horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only vertical
component in the system. See Figure 37.
V Minimum
(meter)
Elbow Only
(0.305)
(0.610)
(0.914)
(1.219)
15