3.4 Command 3
Use command 3 to read dynamic variable and loop current.
Response to command 3:
Byte
Format
0 to 3
Float
4
Code
5 to 8
Float
9
Code
10 to 13
Float
14
Code
15 to 18
Float
19
Code
20 to 23
Float
2ma = 10%
4ma = 20%
20ma = 100%
Description
Primary Variable Loop current (Unit in milli-ampere)
0 ma
: PCB fault, Voltage fault, temperature fault,
relay fault.
2 ma
: Optical Self Test fail & Lid Off fault.
4 ma
: Normal.
20 ma : Alarm
Unit code for ma . Variable 1
Variable 1. Voltage Fault
4 ma
: Normal
20ma
:Voltage Fault (either too low or too high)
Unit code for ma. Variable 2
Variable 2. Temperature Fault
4 ma
: Normal
20ma
: Temperature too high.
Unit code for ma. Variable 3
Variable 3. Self test and lid off
4 ma
:Normal
20ma
:Self Test Fail (window dirty) and/or Lid is off.
Unit code for ma. Variable 4
Variable 4. Communication between FSCHCOM
module and the SS4 flame detector.
4 ma
: Normal.
20ma
: Temperature too high.
Page 7 of 14