• Setting
Function (The contact output
Setting
is activated by the definition
constant
specified in H1.02 when the
following situation occurs.)
0
Fault occurred
1
Running
2
Matching command frequency
3
Matching temporary frequency
Defeated matching frequency
4
or higher
Defeated matching frequency
5
or lower
6
Base blocking
7
Over torque detection
8
Reverse RUN
9
Current limiting
10
Speed searching
11
Zero speed
5. Parameters
5-51
Description
Output frequency matches
with command frequency.
U0.01 – F1.09 ¡ Â U0.02 ¡ Â
U0.01 + F1.09
Output frequency matches
with command frequency of
match detection.
F1.08 – F1.09 ¡ Â U0.02,
U0.02 ¡ Â F1.08 + F1.09
Output frequency is higher
than the frequency detection
level.
U0.02 ¡ Ã F1.08
Output frequency is lower than
the frequency detection level.
U0.02 ¡ Â F1.08
Blocking the output(during the
contact in putting).
Occurring the over torque
(OL3).
Occurring the current(torque)
limiting.
Searching the speed.
MOSCON-E7 User's Manual
5-52
5.7.3 Multi-function analog input
H2.01~H2.07 are used to configure the function of analog inputs.

5.7.3.1 Analog input form : H2.01

Parameter
Name
Unit
No.
Analog Input
H2.01
-
Type
• H2.01 is used to configure the function of the analog input when
H2.05=0(frequency command).
• Setting
Setting
Function
constant
0
Frequency Command Vin(Voltage input) (terminal 9)
1
Frequency Command Ain(Current input) (terminal 10)
2
Frequency Command Vin + Ain (9+10) ¡ Â
3
Frequency Command Vin – Ain (9-10) ¡ Ã

5.7.3.2 Analog input filter time constant : H2.02

Parameter
Name
Unit
No.
Analog Input
H2.02
1ms
Time Constant
• H2.02 is useful when there are noises in the analog input signal.
• As the value in H2.02 is increased, the noise immunity and the response
time to analog input are increased.
Changeable
Setting
Factory
during
range
Setting
operation
0~3
0
X
Fmax
0
Changeable
Setting
Factory
during
range
Setting
operation
0~100
20