MULTIMETER
EPM-04 / 04C / 04CS
Dimensions
79.3mm
10.8
70mm
96mm
Type PR 19 (96x96)
Panel Cut-out
79.3mm
Wall
70mm
91mm
Tip 19
Type PR 19 (96x96)
50mm
GND A B TR
Out 2 Out 1
RS485
Relay output
Auxiliary
Voltage Measurement
Current Measurement
Supply
Inputs
Inputs
U n
~
L1
L2
L3
N
I
I
I
L1
L2
L3
k
l
L1
K
L
k
l
L2
K
L
k
l
L3
K
L
N
K
L
L1
K
L
k
l
L2
System
K
L
k
l
k
l
6
1
2
3
4
5
I
L1
I
I
L2
L3
Current Measurement Inputs
RS485
13 14 15 16
17 18 19 20
GND B A TR
Out 1 Out 2
Output Relay
Auxiliary
Supply
Voltage Measurement Inputs
7
8
9
10
11
12
L1
L2
L3
N
Available only for EPM-04C/04CS
*
Available only for EPM-04CS
**
Note: For CT-25 models:
k: When CT-25 is used, Red cable is connected to k terminal.
l: When CT-25 is used, Black cable is connected to l terminal.
A4034 / Rev.8
30.1
7.6
9.5
60.6
106.0
10.0
26.5
21.5
Type PK 26
53.0
58.0
Summary of the Contact Operations
ALTERNATIVE 1 (U-I)
ALTERNATIVE 2 (H-L)
Current
-->
Under/Over
Voltage
Frequency
Out 1
Current
Phase Seq.
-->
Voltage
Under/Over
Voltage
Out 2
Frequency
-->
Under/Over
Frequency
Phase Seq.
Current
Valid for EPM-04C/04CS
PK-26
System
L3
N
PR-19
8
MULTIMETER
EPM-04 / 04C / 04CS
Precautions for Installation and Safe Usage.........................................................................1
Front Panel and Usage of Buttons.............................................................................1
General Information and Applications.............................................................................1
Using The Buttons............................................................................................2
Transformer Menu (Ctr / trn / Utr / ConnECtýon) ........................................................................2
Output Setting Menu ..............................................................................3
High/Low Current Settings (SP Cur Hý, SP Cur Lo Menu)..........................................3
Instant Trip Function (CUr ýnS trP Menu).................................................................4
High/Low Voltage Settings (SP UoL Hý, SP UoL Lo Menu)..................................4
Hysteresis Settings for High/Low Voltages (U-H Hys, U-L Hys Menu)............5
Frequency Menu .........................................................................................................6
High/Low Frequency Settings (Frq Hý, Frq Lo Menu).............................................6
Hysteresis Settings for High/Low Frequencies (F-H HyS, F-L HyS) ..............................6
Delay-on / Delay-off Time for High/Low Frequencies (Frq ond, Frq oFd)....6
Phase Sequence (Voltage Sequence Menu) and Instant Trip (UoL ýnS trP Menu) Menu ........6
Erasing the Max., Min. and Max. Demand Values (Reset Menu)........................6
-->
Under
Demand Time for Demand and Max. Demand (dE tý Menu)....................................................7
-->
Under
-->
Under
Connection Diagram ................................................................................................8
Output, SP Current and SP Volt menus are available for EPM-04C/04CS; RS-485 menu
is available for EPM-04CS.
PRECAUTIONS FOR INSTALLATION AND SAFE USE
-->
In CT-25 (120A) compliant models, only CT-25 current transformer
Over
must be used.
Over
-->
Other type of CTs have a high risk to damage to device.
Failure to follow those instructions will result in death or serious injury.
-->
Over
- Disconnect all power before working on equipment.
- When the device is connected to the network, do not remove the front
panel.
- Do not try to clean the device with solvent or the like.Only clean with dry
cloth.
- Verify correct terminal connections when wiring.
- Electrical equipment should be serviced only by your component seller.
- Only for rack panel mounting.
- Fuse must be F type and limit value doesnt exceed 1A.
- No responsibility is assured by manufacturer or any of its subsidiaries
for any consequences arising out of the use of this material.
1
2
3
4
5
6
7
8
9
10
21 22 23
INDEX
14
13
15
16
10
19 20
1 ....... Phase LEDs:The LEDs turn on when the voltage value, which is applied
to one of the current inputs, reach 30 V
2 ....... First displays k LED (for L1). Measurement parameter is the unit of kilo
when LED is turned on. ie: kA, kV
3 ....... Display for L1.
4 ....... Second displays k LED (for L2). Measurement parameter is the unit of kilo
when LED is turned on. ie: kA, kV
5 ....... Display for L2.
6 ....... Third displays k LED (for L3). Measurement parameter is the unit of kilo
when LED is turned on. ie: kA, kV
7 ....... Display for L3.
8 ....... Displays network frequency when Hz LED is turned on.
9 ....... k LED for neutral current. Measurement parameter is displayed in unit of
kilo when this LED is turned on.
10 ....... Display for neutral current and frequency (for EPM-04C/04CS).
11 ....... First warning output LED (Out1). Turned on when the output is activated.
12 ....... Second warning output LED (Out2). Turned on when the output is activated.
13 ....... Over current / voltage warning output for L1. (EPM-04C/04CS)
14 ....... Low current / voltage warning output for L1. (EPM-04C/04CS)
15 ....... Over current / voltage warning output for L2. (EPM-04C/04CS)
16 ....... Low current / voltage warning output for L2. (EPM-04C/04CS)
17 ....... Over current / voltage warning output for L3. (EPM-04C/04CS)
18 ....... Low current / voltage warning output for L3. (EPM-04C/04CS)
19 ....... Over current / frequency warning output for frequency and neutral current
(EPM-04C/04CS).
11 12
20 ....... Low current / frequency warning output for frequency and neutral current
(EPM-04C/04CS).
21 ....... Monitoring the L1, L2, L3 voltages values when V LED is turned on and
displays the frequency in 4th display.
13
22 ....... Monitoring the L1, L2, L3 currents values when A LED is turned on and
14
displays the neutral current in 4th display.
23 ....... Indicates the activating delta connection when
15
current protection is disactivated even if is activated.
24 ....... H LED for max. instant current and voltage. Max. instant currents and
16
voltages are displayed when this LED is turned on.
17
25 ....... L LED for min. instant current and voltage. Min. instant currents and
voltages are displayed when this LED is turned on.
18
26 ....... M LED for max. demand. Max. demand values are displayed when this
LED is turned on.
19
27 ....... SET button. It is used to enter into the menu and to save the values.
30
If SET button is pressed for 3 sec. in the measurement mode, you can
enter into menus. This button is used for monitoring the max. (H), Min.
29
(L) current values and max. demand values in measurement mode.
28 ....... Downward selection button.
28
29 ....... Upward selection button.
30 ....... ESC button. Escaping from the menu. And also used for switching off the
27
Latch function while this function has activated.
24
General information
20
25
EPM-04/04C/04CS is designed for measuring Phase current, frequency, neutral
26
current and voltages (Phase-Phase and Phase-Neutral) in a
3-Phase system.
EPM-04C/04CS;
Device has 2 warning output which named as Out1 and Out2. (NO-Normally
Open) Please refer to Output menu for the functions of the relays.
1
3
2
5
4
7
6
1
17
18
30
27
24
8
9
12 11
28
29
25
21 22 23
26
is turned on. Neutral