)LUH =RQHV ² 'HILQLWLRQ
A ILUH ]RQH is the defined area of a building or property to be fire protected. All the
fire detectors monitoring this area are assigned to the ILUH ]RQH. A ILUH ]RQH maybe
monitored by one or more detectors or by all the detectors on a loop.
Fire zones mainly define natural fire cells in the building, and are divided into VXE
]RQHV in order to be able to implement various control requirements within the
same fire zone. Fire zone definition enables you following features:
If loop 01 has 60 detectors, you could assign all of them to the same ILUH ]RQH "01".
As no special control functions are required for this zone, you assign all the 60
detectors to just one VXE ]RQH "0101". See table below
Loop 05 has 95 detectors connected, and as you need for instance to disconnect
detectors 61 to 95 separately, you assign them to two different ILUH ]RQHV ("02" and
"03"). See table below.
In addition, you have different control requirements for the loop 05 detectors:
detectors 01 to 12 must activate certain door retainers, while detectors 13 to 20
will not activate the sounders, etc. You assign then VXE ]RQHV "0201", "0202", etc.
for the different control requirements. See table below.
Required ILUH ]RQH assignments in this example:
01
02
03
Sub Zone 0101
60
04
Fire Zone 01
9
ANX95E control panels have a maximum of 240 fire zones and no sub zones.
ANX95 control panels have no fire zones.
User's Guide '(/7$ 23
2Q WKH GLVSOD\
alarms or pre-alarms from detectors will be referred to their ILUH ]RQH
'XULQJ RSHUDWLRQ
you can test, connect or disconnect ILUH ]RQHV in one operation
:KHQ SURJUDPPLQJ
you will be able to specify the VXE ]RQHV that will activate individual alarm and
control outputs
([DPSOH RI )LUH =RQH $VVLJQPHQWV

)LUH =RQH 1R
6XE =RQH 1R
(max. 256)
01
02
02
02
03
03
61
71
Fire Zone 03
Detector loop 01
'HWHFWRU $GGUHVVHV
(max. 256)
0101
0101 — 0160
0201
0501 — 0512
0202
0513 — 0520
0203
0521 — 0560
0301
0561 — 0570
0302
0571 — 0595
62
70
01
Sub Zone 0301
Sub Zone 0302
95
Fire Zone 02
5 Appendix
12
Sub Zone 0201
Sub Zone 0202
13
20
Detector loop 05
21
Sub Zone
0203
60
39