Check out procedure

Check off steps as completed

❏ ❏
Boiler properly filled with water?
❏ ❏
Boiler piping checked for leaks (including tankless heater, if used)?
❏ ❏
System vents operating properly?
❏ ❏
Boiler properly skimmed?
❏ ❏
Air purged from oil piping? Piping checked for leaks?
❏ ❏
Flue cap in place and tightened? Burner door closed, sealed and nut tight? Burner plugged in and service
switch on?
❏ ❏
Proper draft and burner flame? Final adjustment made with combustion test equipment?
❏ ❏
Test pressure control: While burner is operating, move indicator on limit control below actual boiler steam pres-
sure. Burner should go off. Raise setting on pressure control above steam pressure and burner should re-ignite.
❏ ❏
Test low water cutoff(s): Follow control manufacturer's instructions for testing procedures. Make sure burner
goes off when control responds to low water condition. Burner should re-ignite when proper water level is
restored.
Test additional field-installed controls: If boiler has additional operating control or other controls, test for
❏ ❏
operation as outlined by control manufacturer. Burner should be operating and should go off when controls
are tested. When controls are restored, burner should re-ignite.
Limit control set to system pressure requirements?
❏ ❏
Thermostat heat anticipator setting (if available) set properly? Refer to "Connect wiring," page 24.
❏ ❏
Boiler cycled with thermostat? Raise to highest setting and verify boiler goes through normal start-up cycle.
❏ ❏
Lower to lowest setting and verify boiler goes off.
Observed several operating cycles for proper operation?
❏ ❏
Set room thermostat(s) to desired room temperature?
❏ ❏
Completed Installation and Service Certificate (page 33)?
❏ ❏
Reviewed Maintenance and Service Manual with owner or maintenance person and instructed person to keep
❏ ❏
for future reference?
Returned all instructions provided with boiler to its envelope and placed with boiler for future reference?
❏ ❏
32
SERVICE TECHNICIAN ONLY — read and follow completely.
Obtain gas-tight seal to prevent possible flue gas leakage and carbon monoxide emissions, leading
to severe personal injury or death.
Boiler Manual
Part number 550-141-829/1211

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sgo gold series

Table of Contents