FAN-LIMIT-SAFETY THERMOSTATS SETTING

The thermostats will be supplied with the setting pointed out in the table here under:
FAN thermostat:
LIMIT (1) thermostat
SAFETY (2) thermostat
(1)
The LIMIT thermostat have a permanent setting and do not have to be touched;
The SAFETY Thermostat (Typ 515) need to be set as specified in the manual during the installation.
(2)
To control od re-set the set-point in the different thermostats, operate as hereby descripted:
Contents:
1.
White automatic-manual ventilation switch (where
available).
2.
FAN function electrical connections.
3.
Dual thermostat graduated reading.
4.
Fixture holes.
5. Fans stop temperature flag.
6. LIMIT-SAFETY intervention temperatures flag
7.
Cable grip slits. Inserting a screwdriver the terminal is
released and it is possible to pass the wire. Removing
the end of the screwdriver the terminal locks the wire
auto matically into the
WARNING!
Pull gently on the wire to make sure it is in fact
locked in
place.
All Parts available from
www.sparesgiant.com
8. Fan starts temperature flag.
9. LIMIT-SAFETYfunctions electrical connections.
10.
Red button to release LIMIT response.
01772 329 565
11. Metal bridge (where available).
WARNING!
For the typ 1 the metal bridge 11 must be present.
For the models from typ 2 until typ 15 the metal bridge 11
must be removed.
SAFETY THERMOSTAT SETTING (Typ 515)
The setting have to be done as follows:
Start the equipment in normal running conditions;
Make sure that the burner ist set at the right heating power;
Make sure that the air flow is correct;
As the equipments runs at full capacity, check the air temperature close to the TR safety thermostat sensor
(verifying the positioning of graduated reading), and after this set the intervention temperature at list 15-20
degrees over. For example, if the air temperature would be 40°C, then the thermostat intervention
temperature have to be 60°C.
24
terminal.
25 – 35°C
100°C
Pre-setting 80°C