Toshiba MMY-MAP0804HT8(Z)(ZG)-E Service Manual page 238

Multi type heat pump model cooling only model
Table of Contents

Advertisement

Outdoor Unit
M Pressure sensor characteristics
• Input/output wiring summary
Pin No.
Input/output name
1
OUTPUT
2
3
4
• Output voltage vs. pressure
High pressure side (Pd)
0.5
~
4.3V
0
3.73MPa
~
5
4.3
0.5
0
Indoor Unit
M Temperature sensor characteristics
Indoor TA sensor
30
Resistance
[kΩ]
20
10
0
High pressure side (Pd)
Lead wire color
White
GND
Black
+5V
Red
3.73
4.41
Pressure (MPa)
10
20
30
Temperature [°C]
Low pressure side (Ps)
Input/output name
OUTPUT
GND
+5V
Low pressure side (Ps)
0.5
~
3.5V
0
0.98MPa
~
5
3.5
0.5
5.1
0
0.98
40
50
60
237
Lead wire color
White
Black
Red
1.47
Pressure (MPa)
Temperature [°C] Resistance [kΩ]
0
33.9
5
26.1
10
20.3
15
15.9
20
12.6
25
10.0
30
35
40
45
50
55
60
5.1
8.0
6.4
5.2
4.2
3.5
2.8
2.4