Slant/Fin VSPH-60 Operating Instructions Manual page 27

Victory vsph series direct-vent sealed combustion boilers hot water models
Table of Contents

Advertisement

VICTORY VSPH Models
D. BURNER SHORT CYCLES
CAUSE
1.
Thermostat heat anticipator set too low.
2.
Excessive pressure drop due to excess venting or air
intake system.
3.
Blockage or restriction in venting or air intake system.
4.
Defective air flow switch (out of adjustment).
E. FUMES AND GAS ODORS
CAUSE
1.
Leaks in gas piping or accessories.
2.
Gas leaks in service line or meter connections.
3.
Condensation trap is not full of water.
4.
Venting system is physically damaged.
5.
Over - firing
IF REPLACEMENT PARTS ARE NEEDED
When parts are needed, refer to boiler model and serial number
shown on the boiler name/rating plate. Whenever possible refer
to the original order by number and date.
Control identification and replacement should not be attempted
by unskilled personnel. Only simple, easily-identified controls
and parts may be obtained locally.
APPENDIX A:
a.
Seal any unused openings in the common venting
system.
b.
Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
c.
Insofar as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryer and any appliance not connected
to the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximium speed. DO NOT operate a
summer exhaust fan. Close fireplace dampers.
d.
Place in operation the appliance being inspected Follow
the lighting instructions. Adjust thermostat so appliance
will operate continuously.
e.
Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use the flame of a
Removal of Existing Boiler From Common Vent System
REMEDY
1.
Reset anticipator.
2.
System must be corrected.
3.
Check and Repair
4.
Replace. DO NOT adjust.
REMEDY
1.
Locate leaks and repair.
2.
Close service supply valve - shut down boiler and notify
utility
3.
Check and fill with water.
4.
Check carefully and repair. Also, see "Venting System
Regular Inspection".
5.
Adjust gas input to that shown on boiler rating plate.
All other controls and parts should be identified by
and ordered from Slant/Fin. Relief/Safety valves must
be ASME rated for the pressure and gross output of
the boiler.
For replacement parts, heating contractors should contact their
Slant/Fin boiler distributor.
match or candle, or smoke from a cigarette, cigar or
pipe.
f. After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and
any other gas burning appliance to their previous
conditions of use.
g. Any improper operation of the common venting
system should be corrected so the installation
conforms with the National Fuel Gas Code, ANSI
Z223.1-latest edition or CSA B149.1-00 for natural gas
and propane. When resizing any portion of the
common venting system, the common venting system
should be resized to approach the minimum size as
determined using the appropriate tables in Appendix
G in the National Fuel Gas Code, ANSI Z223.1-latest
edition or CSA B149.1-00 for natural gas and propane.
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vsph-90Vsph-150Vsph-120Vsph-180Victory vsph-180

Table of Contents