II. Initial Start
Safe lighting and other performance criteria were met when
testing various gas manifold and control assemblies used
on the Victory VSPH Series Boilers under the ANSI Z21.13-
latest edition or CSA B149.1-00 for natural gas and
propane.
Instructions
Follow the lighting instructions in this manual. These
instructions are also attached to the boiler.
SAFETY INFORMATION
For Your Safety Read Before Operating
WARNING: If you do not follow these instructions
exactly, a fire or explosion may result causing proper-
ty damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device which
automatically lights the pilot. DO NOT try to light the pilot
by hand.
B. BEFORE OPERATING smell all around the appliance area
for gas. Be sure to smell next to the floor because some
gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• DO NOT try to light any appliance.
• DO NOT touch any electric switch: DO NOT use any
phone in your building.
• Immediately call you gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire depart-
ment.
C.Use only your hand to turn the gas control knob. Never use
tools. If the knob will not turn by hand, don't try to repair it,
call a qualified service technician. Force or attempted repair
may result in a fire or explosion.
D. Do Not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and
any gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which
automatically lights the pilot. DO NOT try to light the pilot
by hand.
5. Remove jacket front panel
6. Turn gas control knob clockwise
DO NOT force.
7. Wait five (5) minutes (longer for propane) to clear out any
gas, then smell for gas, including near the floor. If you
then smell gas, STOP! Follow "B" in the safety information
above on this page. If you don't smell gas, go to next
step.
8. Turn as control knob counterclockwise
9. Replace jacket front panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions "To
Turn Off Gas to Appliance" and call your service technician
or gas supplier.
1. Set thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to
3. Remove jacket front panel.
4. Turn gas control knob clockwise
5. Replace jacket front panel.
Removing Jacket Front Panel
1. Turn black screws
2. Remove front panel.
1. Consult gas supplier for higher heating value* of gas
2. Set thermostat high enough so that boiler will remain on
3. Measure manifold pressure.
to "OFF".
* "Higher Heating" value of gas is commonly known as "heating value".
to "ON".
To Turn Off Gas to Appliance
be performed.
then continue to "OFF". Do not force.
¼
turn to open position.
1
4
To replace the panel, reverse procedure.

Gas Input Rate Adjustment

Gas Valve VR8204 or VR8304
W/m
3
(Btu/cu. ft.)
Correct manifold pressure for gas used is printed on boiler
rating plate. NOTE: Gas pressure may be adjusted by
turning pressure regulator screw on combination gas valve
turn clockwise to increase pressure, counterclockwise to
decrease pressure).
VICTORY VSPH Models
till knob stops,
Figure 19.