W8735D TELEPHONE ACCESS MODULE

Alert Menu

The W8735D alerts user defined abnormal conditions,
EnviraCOM alarms, and control alarms via the telephone. Use
the W8735D Alert menu to set the alert priority level in order
to set dial-out times for low priority alerts, and to retrieve the
last ten alerts from the alert history archive.
From the Main menu, press 4 on the telephone keypad
and follow the voice prompts. See Table 5.
To return to the Main menu, press the * key at any time.
Table 5. W8735D Voice Menu Tree — Alert Settings Menu.
Main Menu
Selection
Sub Menu
(Key-Press) and
Selection
Description
(Key-Press)
4
Alert
1
2
3
1. Setting Alert Priorities
The W8735D is designed to automatically alert the user
and/or contractor based on the alert's selected priority level.
Use the Set Alert Priorities sub-menu to configure each alert's
priority level. See Table 6.
From the Alert menu, press 1 on the telephone keypad
and follow the voice prompts to set the alert priorities.
The W8735D cycles through each alert, announcing the
current priority level and prompting for the new priority level
setting. Follow the voice prompts.
IMPORTANT:
If only standard thermostats or sensors are used (no
EnviraCOM bus activity on any channel) to enunciate
temperature alerts or other abnormal conditions, be
sure to select "No Priority" for "System Alert Priority"
when setting limit priorities. Failure to do this will
result in nuisance "System Alerts".
Table 6. Alert Priority Setting Definitions.
Key
Alert
Press
Priority
9
High
5
Low
1
No Priority
69-2027—01
Sub Menu Description
Set alert priority
FOLLOW
Set low priority dial-out
VOICE
time
PROMPTS
Retrieve alert history
Definition
Dial-out immediately (and every 30
minutes until acknowledged)
Dial-out at user defined time (and repeat
every 24 hours until acknowledged);
factory default time is 3:00 P.M.
No dial-out generated
2. Setting Low Priority Alert Dial-out Times
Set the dial-out time of day as follows:
From the Alert menu, press 2 on the telephone keypad
and follow the voice prompts to set the low priority dial-
out time for each alert.
For low priority alerts, the user may select any hourly
increment from 1 to 23 to specify the hour of the day to dial-
out.
NOTE: The factory default settings for the W8735D are
shown in Table 7. If the Alert Priority is not set, the
settings in Table 7 are used.
Table 7. Factory Default Alert Settings and Descriptions.
Factory
Alert
Priority
Power Outage High
Power Restore Upon
Demand
Low Battery
Low
Auxiliary Input High
Pass Code
High
Change
Indoor Low
High
Temperature
Limit
Indoor High
High
Temperature
Limit
Outdoor Low
High
Temperature
Limit
Outdoor High
High
Temperature
Limit
Air Filter
Low
Humidity Low
High
Limit
Humidity High
High
Limit
System Failure High
a
While in sleep mode, no W8735D functions are available.
b
This feature is enabled by the user during a power outage
alert call.
16
Factory
Setting
Description
N/A
Power was out at this
location for more than one
hour.
The W8735D dials-out only
once and then goes into
sleep mode until power is
a
restored.
Not
The W8735D dials-out once
Requested
power is restored.
b
N/A
Optional auxiliary input
sensor has tripped.
N/A
Optional auxiliary input
sensor has tripped.
3:00PM dial-
The pass code has been
out
altered.
50º F
The room temperature
(10° C)
dropped below the low limit
setting.
90º F
The room temperature
(32° C)
exceeded the high limit
setting.
40º F
The outdoor temperature
(4° C)
dropped below the low limit
setting.
105º F
The outdoor temperature
(40° C)
exceeded the high limit
setting.
3:00PM dial-
Change air/duct filter.
out
25%
The indoor humidity
dropped below the low limit
setting.
70%
The indoor humidity
exceeded the high limit
setting.
N/A
Communication failure or
system lockout.