Modine Manufacturing HSB Installation And Service Manual

Modine Manufacturing HSB Installation And Service Manual

Steam/hot water unit heaters

Advertisement

Model HSB
Horizontal Delivery
Top/Bottom
Inlet/Outlet
Models V/VN
Vertical Delivery
IMPORTANT
The use of this manual is specifically intended
for a qualified installation and service agency.
A qualified installation and service agency must
perform all installation and service of these
appliances.
Inspection On Arrival
1. Inspect unit upon arrival. In case of damage, report it
immediately to transportation company and your local factory
sales representative.
2. Check rating plate on unit to verify that power supply meets
available electric power at point of installation.
3. Inspect unit received for conformance with description of
product ordered (including specifications where applicable).
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
INSTALLATION AND SERVICE MANUAL
Model HC
Horizontal Delivery
Side
Inlet/Outlet
Model PT/PTN
"Power-Throw"
THIS MANUAL IS THE PROPERTY OF THE OWNER.
steam/hot water unit heaters
®
C
US

General Information

Installation and service instructions in this manual are applicable
to the three types of steam/hot water unit heaters which should
be installed in their proper applications for their most effective
function as overhead heating units.
The copper coils are warranted for operation at steam or
hot water pressures up to 150 lbs. per sq. in. gauge, and
or temperatures up to 375°F, cupronickel tube units are
warranted for operating pressures up to 250 PSI and operating
temperatures up to 400°F. Canadian Standards Association
(CSA) requriements state that explosion-proof units may not
be used with a fluid temperature in excess of 329°F and still
maintain their explosion-proof rating, for national electric code
ignition temperature rating T3B for grain dust.
Motors are designed for continuous duty. They can operate in a
maximum ambient temperature of 104°F (40°C).
The unit heaters are listed by the Canadian Standards
Association as certified and Canadian Registered heat
exchangers CRN OH 9234.5C. *Does not apply to V/PT 952.
CAuTION
Do not remove outlet fan guard from vertical
type unit heaters.
Steam horizontal and vertical delivery unit heaters are available
in both standard and low-outlet temperature models. Low outlet
temperature models are recommended primarily for installation
on heating systems with steam pressures of 30 to 150 PSI.
When used at these steam pressures they provide lower outlet
air temperatures for longer heat throw and, because of wider
fin spacing, they are less susceptible to clogging in dusty
atmospheres.
The model number of each unit heater indicates its rated Btu/Hr.
capacity/1000 at 2 lbs. steam pressure and 60°F entering air
temperature. For example an HSB 63 has an output of 63,000
Btu/Hr. at 2 lbs. steam and 60°F entering air.
1-550.28
5H0707180000
September, 2014

Advertisement

Table of Contents
loading

Summary of Contents for Modine Manufacturing HSB

  • Page 1: General Information

    2 lbs. steam pressure and 60°F entering air available electric power at point of installation. temperature. For example an HSB 63 has an output of 63,000 Btu/Hr. at 2 lbs. steam and 60°F entering air. 3. Inspect unit received for conformance with description of product ordered (including specifications where applicable).
  • Page 2: Table Of Contents

    25.4 replacement parts list may be obtained by contacting CFH (ft /hr) 0.00000787 pound 0.454 Modine Manufacturing Company. Refer to the rating plate CFM (ft /min) 0.0283 /min psig 6.89 on the appliance for complete appliance model number, CFM (ft /min) 0.000472...
  • Page 3: Not Be Installed Where They May Be Exposed To A Potentially

    UNIT LOCATION / UNIT MOUNTING UNIT LOCATION figure 3.3 - Combination Horizontal and Vertical Delivery Unit Installation dANgeR Appliances with power codes 01, 02, 04, 05, and 10 must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
  • Page 4 — ➀ With horizontal louvers opened 30° from the vertical plane. HSB units have top and bottom piping connections, HC units have side connections. All have copper tubes. ➁ V and PT models have copper tubes, VN and PTN models have cupronickel tubes. Mounting heights are maximum for heaters operating at standard conditions (2 lbs.
  • Page 5: Disconnect Power Supply Before Making Wiring Connections

    Models HSB 18 and HSB 24, have two heating coil if located in an area subject to freezing. tapped holes in the top for unit suspension. HSB 18 and HSB 24 3. In steam or hot water systems, rapid air removal is required models do not require independent suspension and are installed because entrained air is a cause of corrosion.
  • Page 6: Operation

    (HSB/HC, PT/PTN) or top (V/VN) of the unit heater. by heat from the unit or other sources of drafts that would Automatic Control Operations prevent it from properly controlling room temperature.
  • Page 7: General

    OPERATION figure 7.1 - Horizontal Delivery Unit Cutaway Connections — Female-type permits direct connection of unit heater to the piping. HC models have copper connectors at side of the unit. Vertical fins — Less opportunity for dust and dirt to collect. Reduces cleaning. Fins die-formed for added strength and heat transfer.
  • Page 8: Performance Data

    Model No. Btu/hr Mounting or Spread @ Condensate Approx. Velocity Temp. Height (ft.) Max. Height lb/hr ‚ (fpm) (°f)   HSB/HC 18 18,000 1/60 1,550 HSB/HC 24 24,000 1/25 1,550 HSB/HC 33 33,000 1/25 1,550 HSB/HC 47 47,000 1/12 1,550...
  • Page 9 Model No. Btu/hr Mounting or Spread @ Condensate Approx. Velocity Temp. Height (ft.) Max. Height lb/hr ‚ (fpm) (°f)   HSB/HC 18L 15,900 1/60 1,550 HSB/HC 24L 19,300 1/25 1,550 HSB/HC 33L 29,500 1/25 1,550 HSB/HC 47L 32,000 1/12 1,550...
  • Page 10 Spread @ Approx. Velocity Temp. (ft. of Height (ft.) Max. Height ‚ (fpm) (°f) Water)   HSB/HC 18 12,600 0.3 / 5.0 1/60 1,550 HSB/HC 24 16,200 0.3 / 5.0 1/25 1,550 HSB/HC 33 21,700 0.4 / 10.0...
  • Page 11 Horizontal Delivery HSB/HC 108L 66,100 0.8 / 30.0 2,150 1,625 HSB/HC 121L 66,700 0.8 / 30.0 2,070 1,075 HSB/HC 165L 113,200 11.8 2.0 / 30.0 3,480 1,075 HSB/HC 258L 147,400 15.4 2.5 / 70.0 4,655 1,075 HSB/HC 290L 161,100 16.8 2.5 / 70.0...
  • Page 12: Dimensional Data

    H (PIPE CONNECTION) Wall 5" 5" Min. ➀ Vertical deflector blades shown are standard on models HC 258-340 Table 12.1 - Model HSB and HC Dimensions ➀ ➁ and optional on model HC 193. female Approx. Model 115 Std. 115V Exp.
  • Page 13 DIMENSIONAL DATA figure 13.1 - Model Dimensions V/VN and PT/PTN Vertical Air Delivery “Power-Throw” Air Delivery Air Deflectors (Optional) Table 13.1 - Model V/VN and PT/PTN Dimensions ➀ ➁ ➂ Male Connections Approx. Model Shipping Number Diameter Bottom Wt. (lb.) V/VN 42 24-3/4 3-5/8...
  • Page 14: Motor Ampere Ratings

    ➁ All motors include thermal overload protection except for units with power code 04, 05, or 10. ➂ All HSB/HC units, V/VN 42 thru V/VN, PT/PTN 333 motor HP listed for power code 01. V/VN, PT/PTN 333 thru V/VN, PT/PTN 610 motor HP listed for power code 04 and V/PT 952 motor HP listed for power code 05.
  • Page 15: Service / Troubleshooting

    SERVICE / TROUBLESHOOTING Casings 2. For thorough cleaning of coil, remove motor and fan and spray a mild alkaline cleaning solution over the coil. After a Periodic cleaning of casings is recommended to remove few minutes, follow by a hot water rinse. (A steam gun can be dirt, grease and corrosive substances that may injure finish.
  • Page 16: Warranty

    Burners High Intensity Infrared Units Sheet Metal Parts All Products As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice. Modine Manufacturing Company 1500 DeKoven Avenue Racine, WI 53403 Phone: 1.800.828.4328 (HEAT)