Sidewall Venting - International comfort products N8MSN Installation Instructions Manual

80% single stage, psc motor, category i, gas furnace
Table of Contents

Advertisement

The vent connector can exit the cabinet of the furnace
through one of five locations.
1. Attach the single wall vent connector to the furnace
vent elbow, and fasten the vent connector to the vent
elbow with at least two field−supplied, corrosion−resist-
ant, sheet metal screws located 180_ apart.
NOTE: A flue extension is recommended to extend from the
furnace elbow to outside the furnace casing. If flue extension
is used, fasten the flue extension to the vent elbow with at
least two field−supplied, corrosion−resistant, sheet metal
screws located 180_ apart. Fasten the vent connector to the
flue extension with at least two field−supplied, corrosion
resistant sheet metal screws located 180_ apart.
2. Vent the furnace with the appropriate connector as
shown in Figure 28 − Figure 40.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal
injury. Sheet metal parts may have sharp edges or
burrs.
Use care and wear appropriate protective clothing,
safety glasses and gloves when handling parts and
servicing furnaces.
3. Determine the correct location of the knockout to be re-
moved.
4. Use a hammer and screwdriver to strike a sharp blow
between the tie points and work the slug back and forth
until the slug breaks free.
FURNACE ORIENTATION
Downflow
Horizontal Left
Horizontal Left
Horizontal Left
Downflow
Downflow
* 4 in. (102 mm) inside casing or vent guard
** Including 4 in. (102 mm) vent section (s)
NOTE: All vent configurations must also meet National Fuel Gas Code (NFGC) venting requirements
NOTE: For all unlisted vent configurations, refer to National Fuel Gas Code (NFGC) venting requirements.
441 01 1402 02
Table 10—Minimum Vent Heights
VENT
ORIENTATION
Vent Elbow left,
then up Figure 32
Vent Elbow right,
then up Figure 35
Vent Elbow up
Figure 36
Vent Elbow up
Figure 36
Vent elbow up then left
Figure 30
Vent elbow up, then right
Figure 33
CAUTION
!
BURN HAZARD
Failure to follow this caution may cause personal
injury.
Hot vent pipe is within reach of small children when
installed in downflow position. See the following
instruction.
An accessory Vent Guard Kit is REQUIRED for downflow
applications for use where the vent exits through the lower
portion of the furnace casing door. Refer to the Vent Guard Kit
Instructions for complete details.
The horizontal portion of the venting system shall slope
upwards not less than 1/4−in. (6 mm) per linear ft. (21 mm/m)
from the furnace to the vent and shall be rigidly supported
every 5 ft. (1.5 M) or less with metal hangers or straps to
ensure there is no movement after installation.

SIDEWALL VENTING

This furnace is not approved for direct sidewall horizontal
venting.
Per section 12.4.3 of the NFPA 54 / ANSI Z223.1−2009, any
listed mechanical venter may be used, when approved by the
authority having jurisdiction.
Caution!! for the following applications, use the minimum
vertical vent heights as specified below.
For all other applications, follow exclusively the national fuel
gas code.
MINIMUM VENT
FURNACE
DIAMETER IN.
INPUT (BTUH/HR)
154,000
132,000
110,000 (3 ton only)
154,000
132,000
154,000
132,000
154,000
110,000 (3 ton only)
110,000 (3 ton only)
MINIMUM VERTICAL
VENT HEIGHT
(mm)*
FT. (M)**
5 (127)
12 (3.6)
5 (127)
7 (2.2)
5 (127)
7 (2.2)
5 (127)
7 (2.2)
5 (127)
10 (3.0)
5 (127)
10 (3.0)
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

N8msl

Table of Contents