Simplicity 64
Simplicity 126
&
7. To check that the panel has read all the devices on
loop 1, select option 1 Lp1 Dev. If the loop contents
are as expected, go to point 8, otherwise go to
Loop Contents Fault Finding on page 16.
8. Press cancel to leave the menu. The panel is now configured, and will function as a
basic system, (press 6 for covered), but it is more useful to enter device labels, to give a
more precise location of an alarm device. We recommend that the device labels be
entered to allow the panel to be more user friendly during normal operation.
9. Select option 4 for message editing. The panel
will now ask for its write enable switch to be set to
the on position . (This is the dip switch on the CPU
board, switch 1).
10. The panel will now ask for the loop number, and
the loop address of device name to be entered. Press
enter to confirm loop 1, and enter again to confirm
address 001. Enter the device label using the built in
keyboard. The label can be 20 characters long,
so try to be as descriptive as possible. Use the caps
lock for capital letters. The delete button is used to
correct mistakes. When the label has been entered,
record the device type & label in the system setup
chart in the user manual. Press enter 3 times to move to the next device (or enter the loop
number and address to move forward several places.
12 When all devices have been entered, press Cancel
to exit the message editing screen. The panel will ask
for the write enable switch to be set back to the off
position .
NOTE: IF THE PANEL IS POWERED DOWN WITH THE WRITE ENABLE SWITCH ON,
IT WILL ERASE THE DEVICE LABELS WHEN IT IS RE-POWERED.
The panel is now configured and ready for operation.
Approved Document No: GLT.MAN-107
Issue : 1.04
Authorised: GH
INSTALLATION MANUAL.
Date: 05/10/2004
CO
00‌SCC 14‌Loop 1
I/O 01‌ION 00‌DAD 00
ZMU 00‌OPT 45‌Cancel
HET 03‌BGU 05‌= Exit
Please Set The
Write Enable Switch
To the On Position
Message Editing
Loop:1
Address:001
Floor 1. Bedroom 20
Can: Exit
Ent: Next
Please Set The
Write Enable Switch
To the Off Position
PAGE 15