Download Print this page

Table Of Contents; General; Technical Data - Telca TAC-12D-10 Service Manual

Advertisement

Contents:
1.
2.
3.
4.
5.
6.

1. General

The cooling circuit is designed in the form of a maintenance-free, hermetically sealed
system. The cooling unit is filled with the required quantity of refrigerant at the factory,
checked for leaks, and subjected to a functional test run. The installed maintenance-free
fans are mounted on ball bearings, protected against moisture and dust, and fitted with a
temperature monitor. The life expectancy is at least 30,000 operating hours. The cooling
unit is thus largely maintenance-free. All that may be required from time to time is to
clean the components of the external air circuit using a vacuum cleaner or compressed
air if they become visibly dirty.
Maintenance interval: 12 months . Depending on the level of contamination in the
ambient air, the maintenance interval may be reduced to suit the air pollution intensity.

2. Technical data

Model No.
Dimensions WxHxD
Cooling output @L35/L35
Heating output
Rated voltage Volt/Hz
Rated current
Temperature range
Power consumption
Air circuit (External)
Air circuit (Internal)
Noise
Refrigerant
Protection category
Weight
Special voltages available on request.
TAC-12D-10
420 x 1000 x 180 mm
1200 W
1000 W
220VAC, 50/60Hz
3.3 A (Cooling)
4.5 A (Heating)
-40°C ~ +55°C
720 W (Cooling)
1000 W (Heating)
3
570 m
/h
3
450 m
/h
62dB
R134a
IP55
34Kg
Service manual: TAC-12D-10
1/9

Hide quick links:

Advertisement