SC720/SC820
Introduction
1.3
Listings and Standards
1.3.1
UL Listing
The SAFECOM SC720/SC820 Data Repeater system is Listed by Underwriters Laboratories (UL) as follows:
Application and Category
Central Station Burglar Alarm Units
•
COMMERCIAL BURGLARY - AA" Rating
Central Station "Police Connect" Mercantile
•
"AA" Rating
Control Units for Fire Protective Signaling Systems
•
"COMMERCIAL FIRE" Rating
Proprietary Burglar Alarm System Units
•
PROPRIETARY BURGLARY - AA" Rating
Household Burglar Alarm Units
•
"RESIDENTIAL BURGLAR ALARM" Application
Household Fire Warning System Units
•
"RESIDENTIAL FIRE " Application
Process Management Systems
•
Service: "Non-Critical Applications"
1.3.2
NFPA Standards
The SAFECOM SC720/SC820 Data Repeater system meets the following NFPA Standards:
Application
Central Station Signaling Systems
Auxiliary Protective Signaling Systems
Remote Station Protective Signaling Systems
Proprietary Protective Signaling Systems
In accordance with NFPA No. 71 and UL Requirements the maximum number of subscriber control units
(SAFECOM Remote Communications Panels) that a single SAFECOM SC720/SC820 Data Repeater can
monitor for Fire and/or Burglary Applications is "512."
If the number of subscriber control units exceeds 512, a second SC720/SC820 Data Repeater will be required to
monitor and control the additional units.
If the SAFECOM system is configured with more than one (1) SC720/SC820 Data Repeater, the number of
subscriber control units that can be monitored and controlled is UNLIMITED.
90007-201C
Table 2: UL Listings
Table 3: NFPA Standards
SC720/SC820 Operation and Installation Guide
Page 6
Listing
Standard
UL 1610
UL 365
UL 864
UL 1076
UL 1023
UL 985
UL 864
Standard No.
NFPA No. 71
NFPA No. 72B
NFPA No. 72C
NFPA No. 72D
© 2004 Bosch Security Systems