• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidifica-
tion operation and 4-min compressor off repeat.
Compressor ON Temp.
Compressor OFF Temp.
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation(H/P model)
• When the intake air temp reaches +3°...above the setting temp, the compressor is turned off. When below
the setting temp, the compressor is turned on.
Compressor ON Temp.
Compressor OFF Temp.
• While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C , it
operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it oper-
ates with Super-Low(while in sleep mode, with the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it
operates with the low airflow speed.
• If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the
outdoor fan is turned on/off according to the indoor pipe temp.
• While in defrost control, both of the indoor and outdoor fans are turned off.
Defrost Control(H/P model)
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from
starting of heating operation and more than 10 minutes operation of compressor.
• Defrost ends after 9/6 minutes passed from starting of defrost operation or after the outdoor fan operates
within max. 2 minutes 30 seconds when the outdoor pipe temperature rises over 12°C even it before 12 min-
utes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed
from ending of the first defrost and more than 10 minutes operation of compressor.
Heating overload(H/P models)
• Outdoor fan ON/OFF by sensing outdoor pipe temperature.
• Outdoor fan is OFF if pipe temperature is over 6.5°C and outdoor fan is ON if pipe temperature is below 0°C.
• Outdoor fan is off if any one part is heating overload condition.
Setting Temp+0.5°C
Setting Temp-0.5°C
Setting Temp.
Setting Temp.+3°C
-14-