Outdoor Coil, Indoor Coil, And Condensate Drain Pan; Outdoor Fan; Electrical Controls And Wiring - Carrier 50VL-A Performance Installation Instructions Manual

14 seer single-packaged air conditioner system with puron (r-410a) refrigerant single and three phase 2 - 5 nominal tons (sizes 24 - 60)
Table of Contents

Advertisement

A
MAX DISTANCE BETWEEN TOP OF FAN GRILLE AND BOTTOM OF FAN BLADE
SIZE
24
30
36
42
48
60
Fig. 17 - - Unit Access Panels

Outdoor Coil, Indoor Coil, and Condensate Drain Pan

Inspect the condenser coil, evaporator coil, and condensate drain
pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean
the coils either before or after each cooling season. Remove all
obstructions, including weeds and shrubs, that interfere with the
airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint,
clean the coils with a vacuum cleaner, using the soft brush
attachment. Be careful not to bend the fins. If coated with oil or
grease, clean the coils with a mild detergent and water solution.
Rinse coils with clear water, using a garden hose. Be careful not to
splash water on motors, insulation, wiring, or air filter(s). For best
results, spray condenser coil fins from inside to outside the unit. On
units with an outer and inner condenser coil, be sure to clean
between the coils. Be sure to flush all dirt and debris from the unit
base.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain trough with
clear water. Do not splash water on the insulation, motor, wiring, or
MOTOR
Fig. 16 - - Fan Blade Position
Control
Blower
Access
Access
Panel
Compressor
Panel
Access Panel
A09214
MOTOR SHAFT
"A"
IN.
6.3
6.3
7.3
7.6
7.6
7.6
air filter(s). If the drain trough is restricted, clear it with a
"plumbers snake" or similar probe device.

OUTDOOR FAN

CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit
components.
Keep the condenser fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit.
1. Remove 6 screws holding condenser grille and motor to top
cover.
2. Turn motor/grille assembly upside down on top cover to
expose the fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen the setscrew and slide the
fan off the motor shaft.
5. When replacing fan blade, position blade as shown in Fig.
16.
6. Ensure that setscrew engages the flat area on the motor shaft
when tightening
7. Replace grille.

Electrical Controls and Wiring

Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit.
Remove access panels (see Fig. 17) to locate all the electrical
controls and wiring. Check all electrical connections for tightness.
Tighten all screw connections. If any smoky or burned connections
are noticed, disassemble the connection, clean all the parts, restrip
the wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace the
access panels (see Fig. 17). Start the unit, and observe at least one
complete heating cycle and one complete cooling cycle to ensure
proper operation. If discrepancies are observed in either or both
operating cycles, or if a suspected malfunction has occurred, check
24
FAN GRILLE
MM
160
160
185
193
193
193
A08505