Heat Transfer MUNCHKIN Operating Manual page 26

High efficiency heater with the 925 controller
Table of Contents

Advertisement

Standard Munchkin boiler
Retrofit piping (zoning with valves)
Space heating mode
make-up water
purging
valves
NOTES:
This drawing is meant to show system piping concept only.
1.
Installer is responsible for all equipment & detailing required by local codes.
2.
Adjust flow bypass valve for the following minimum boiler flow rates in any operating mode:
Munchkin model T50M: 3 gpm
Munchkin model T80M: 3 gpm
Munchkin model 80M: 3 gpm
Munchkin model 140M: 5 gpm
Munchkin model 199M: 7 gpm
3.
The minimum pipe size for connecting a Super Stor water heater is 1 inch.
4.
The minimum pipe size for connecting a Munchkin boiler is 1.25 inches.
5.
All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.
6.
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.
7.
Install a minimum of 12 diameters of straight pipe upstream of all circulators.
8.
A purging valve may be used in lieu of the ball valve / hose bib combination shown
NOTE: FOR VISION PIPING APPLICATIONS, REFER TO THE VISION INSTALLATION PIPING DIAGRAMS.
Fig. 5-3
26
zone valves
P1
T/P
Munchkin boiler
.
V1
OFF
anti-scald
mixing valve
Super Stor
indirect DHW tank
PIPING
Drawing 1A
flow
bypass
valve
cold