Midea MSV1-09HRDN1-QC2A Service Manual page 41

Air conditioner dc inverter split wall-mounted type
Table of Contents

Advertisement

10.3.5 Temperature Sensors.
Room temp.(T1) sensor,
Indoor coil temp.(T2) sensor,
Outdoor coil temp.(T3) sensor,
Outdoor ambient temp.(T4) sensor,
Compressor exhaust temp.(Te) sensor.
Measure the resistance value of each winding by using the multi-meter.
Some frequently-used R-T data for T1,T2,T3 and T4 sensor:
Temperature ( )
Resistance Value (K )
Some frequently-used R-T data for Te sensor:
Temperature (℃)
Resistance Value (K )
K
5
10
15
26.9
20.7
16.1
5
15
25
141.6
88
56.1
20
25
30
12.6
10
8
35
60
70
36.6
13.8
9.7
40
50
60
5.2
3.5
2.4
80
90
100
6.9
5
3.7
38